| 2016-09-22 17:28:12 | RESIDENTIAL (R3) ALTERATION BUILDING REVIEW COMMENTS. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) |
| | FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED |
| | PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY |
| | IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT |
| | CODE. |
| | |
| | 2- DESIGN PRESSURES FOR G2 DOOR DON'T CORRESPOND TO |
| | EXPOSURE "D". REVISE DESIGN PRESSURES SHOWN ON SHEET |
| | A-3 AND A-3.10. SEC. R301.1 FBC-RESIDENTIAL, 5TH |
| | EDITION (2014). |
| | |
| | 3- DESIGN CRITERIA ON SHEET SP-1.0 REFERENCES ASCE |
| | 7-14. THE ASCE REFERENCED IN THE FBC 2014 IS THE ASCE |
| | 7-10 NOT 14. REVISE AS REQUIRED. CHAPTER 553 F.S. |
| | |
| | 4- GARAGE IS NOT ALLOWED TO BE CONNECTED TO A ROOM THAT |
| | IS USED FOR SLEEPING. ACCORDING TO PLANS SUBMITTED THE |
| | GARAGE IS LEADING DIRECTLY TO AN SLEEPING AREA ON THE |
| | SECOND FLOOR. REVISE AS REQUIRED TO COMPLY WITH THIS |
| | REQUIREMENT.. ALSO, PROVIDE COMPLIANCE WITH THE |
| | DWELLING/GARAGE OPENING PROTECTION AS REQUIRED BY SEC. |
| | R302.5.1 FBC-RESIDENTIAL. PROVIDE COMPLETE |
| | SPECIFICATIONS FOR THE TYPE OF DOOR AND INCLUDE THE |
| | SELF CLOSING DEVICE. |
| | |
| | 5- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | CONSTRUCTION AND INSTALLATION OF FABRIC AWNINGS SHOWN |
| | ON THE PROPOSED SOUTH ELEVATION. SEC. R301.1 |
| | FBC-RESIDENTIAL. |
| | |
| | 6- PROVIDE DETAILS/SPECIFICATIONS FOR THE ROOF SLOPE TO |
| | SHOW COMPLIANCE WITH THE 1/4 PER FOOT SLOPE REQUIRED BY |
| | SEC. R905.11.1 FBC-RESIDENTIAL. REVISE SPECIFICATIONS |
| | FOR THE ROOF TRUSSES SHOWN ON WALL SECTION ON SHEET |
| | A-3.21 AND CLEARLY PROVIDE THE SPECIFICATIONS ON THE |
| | STRUCTURAL DRAWINGS. |
| | |
| | 7- PROVIDE ICYNENE FOAM INSULATION ICC EVALUATION |
| | REPORT (2 COPIES) SHOWING COMPLIANCE WITH SEC. R316 |
| | FBC-RESIDENTIAL. DESIGNER OF RECORD TO REVIEW/APPROVE |
| | PRIOR TO SUBMITTAL. |
| | |
| | 8- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | CONSTRUCTION AND INSTALLATION OF STAIRWAY SHOWING |
| | COMPLIANCE WITH THE LIVE LOADS OF TABLE R301.5 AND THE |
| | REQUIREMENTS OF SEC. R311.7 FBC-RESIDENTIAL. |
| | |
| | 9- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY |
| | SPECIFY MULLION SIZE TO VERIFY COMPLIANCE WITH THE |
| | CALCULATED DESIGN PRESSURES. |
| | |
| | B) OPAQUE FIBERGLASS DOOR AS SPECIFIED ON PLANS. NOTE: |
| | PROVIDE CURRENT PRODUCT APPROVAL DRAWINGS DRAWING |
| | FL-17184-11 SUBMITTED IS FOR THE 2010 FBC. SEE GENERAL |
| | NOTE #1 ON PAGE 1 OF 7. NEED TO PROVIDE PRODUCT |
| | APPROVAL FOR THE CURRENT 2014 FBC. NOTE: VERIFY THAT |
| | PRODUCT APPROVAL MEETS THE G2 DOOR REVISED DESIGN |
| | PRESSURES. |
| | |
| | C) ALL USP AND SIMPSON STRUCTURAL CONNECTORS SPECIFIED |
| | ON THE TRUSS ANCHOR SCHEDULE AND ALL OTHER DETAILS. |
| | UPDATE THE FLORIDA PRODUCT APPROVAL NUMBER LISTED ON |
| | THE TRUSS ANCHOR SCHEDULE. NEED THE 2014 CODE VERSION |
| | NOT THE 2010 CODE VERSION. AND, LIST THE FLORIDA |
| | PRODUCT APPROVAL NUMBER NEXT TO EACH CONNECTOR |
| | SPECIFIED ON THE DETAILS PROVIDED. |
| | |
| | 10- DESIGNER OF RECORD TO APPROVE ALL PRODUCT APPROVALS |
| | AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 11- FLAT ROOF MODIFIED BITUMEN NOA 14-0529.02 |
| | SUBMITTED: CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS |
| | GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE |
| | DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. NOTE: |
| | IF SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES |
| | FOR ALL ROOF ZONES, THEN SIGNED AND SEALED RAS 117 |
| | CALCULATIONS WILL BE REQUIRED. ONLY ASSEMBLIES WITH |
| | GENERAL LIMITATION #7 WILL ALLOW RAS 117 CALCULATIONS. |
| | ASSEMBLIES WITH GENERAL LIMITATION #9 DON'T ALLOW RAS |
| | 117 CALCULATIONS. SEE LAST PAGE OF NOA SUBMITTED. |
| | |
| | 12- TRUSS PACKAGE SUBMITTED: |
| | A) COVER PAGE NEEDS THE INFORMATION OF THE STRUCTURAL |
| | ENGINEER OF RECORD AS REQUIRED BY 61G15-31.003 FAC. |
| | |
| | B) THE INDIVIDUAL TRUSS DRAWINGS NEED THE TITLE BLOCK |
| | OF THE TRUSS ENGINEER AS REQUIRED BY 61G15-31.003 FAC. |
| | |
| | C) TRUSS PACKAGE NEEDS TO BE APPROVED BY THE ENGINEER |
| | OF RECORD AS REQUIRED BY 61G15-30.005 FAC. |
| | |
| | NOTE: THERE ARE TWO ADDITIONAL COPIES OF STRUCTURAL |
| | DRAWINGS S01 AND S02 DWGS ON ONE SET. PLEASE REMOVE ONE |
| | COPY. |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWING. DON'T STAPLE OLD DRAWINGS TO RESUBMITTED SETS. |
| | SUBMIT OLD DRAWINGS FOR REFERENCE. |
| | |