| Notes |
| Date |
Text |
| 2016-09-07 09:15:25 | 4316 BRAXTON AVENUE | | | PERMIT #16081241 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PROVIDE PERMANENT WEATHERPROOF EXIT SIGNS ON EACH EACH | | | EXIT GATE. | | | | | | DOORS/GATES SERVING AN ASSEMBLY SPACE WITH AN OCCUPANT | | | LOAD OF 50 OR MORE PERSONS SHALL BE EQUIPPED WITH PANIC | | | HARDWARE. | | | | | | THE OCCUPANT LOAD FOR THE POOL DECK SPACE IS | | | INCORRECTLY CALCULATED USING AN OCCUPANT LOAD FACTOR OF | | | 50 SQ.FT. PER PERSON. PER NFPA 101 TABLE 7.3.1.2 AN | | | OCCUPANT LOAD FACTOR OF 30 SQ.FT. PER PERSON SHALL BE | | | USED. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | | | | |
|