| Plan Review Notes For Permit 16081202 |
| Permit Number |
16081202 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-09-02 07:51:43 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE INSTALLATION DRAWINGS ARE REQUIRED TO HAVE THE | | | FLORIDA ENGINEER'S SEAL AND ORIGINAL HANDWRITTEN | | | SIGNATURE, COPIES OR OTHER FACSIMILES ARE NOT | | | ACCEPTABLE. FAC 61G15 - 23.002 DIGITAL SIGNATURES ARE | | | ONLY ACCEPTABLE FOR ELECTRONICALLY TRANSMITTED PLANS | | | AND DOCUMENTS. | | | | | | 2) SPECIFY THE SIZE OF THE ROOF TOP COLLECTOR ON THE | | | PLANS. FBC 107.2.1 | | | | | | 3) SPECIFY THE TILT UP ANGLE ABOVE THE ROOF PLANE OF | | | THE ROOF TOP COLLECTOR ON THE PLANS. IF IT IS GREATER | | | THAN 15 DEGREES ABOVE THE ROOF PLANE, SUBMIT SITE | | | SPECIFIC ENGINEERING. FBC 107.2.1 |
|