| 2016-09-14 13:57:10 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16081192 |
| | ADD: 1200 S. FLAGLER DR. SUITE # 1503 |
| | CONT: CAMBRIDGE |
| | TEL: 561-784-3722 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | 09/14/2016 |
| | ACTION: APPROVED AS NOTED HEREIN. |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.3.4.3 CERTIFICATIONS BY CONTRACTORS |
| | AUTHORIZED. |
| | |
| | PLANS ARE NOT CLEAR AS TO WHAT TYPE OF BACKING BOARD |
| | WILL BE USED AROUND THE TUB SURROUND. PLEASE |
| | DEMONSTRATE TO THE INSPECTOR COMPLIANCE WITH: |
| | 2014 FBC-B 2509.2 BASE FOR TILE. GLASS MAT |
| | WATER-RESISTANT GYPSUM BACKING PANELS, DISCRETE |
| | NONASBESTOS FIBER-CEMENT INTERIOR SUBSTRATE SHEETS OR |
| | NONASBESTOS FIBER-MAT REINFORCED CEMENTITIOUS BACKER |
| | UNITS IN COMPLIANCE WITH ASTM C 1178, C 1288 OR C 1325 |
| | AND INSTALLED IN ACCORDANCE WITH MANUFACTURER |
| | RECOMMENDATIONS SHALL BE USED AS A BASE FOR WALL TILE |
| | IN TUB AND SHOWER AREAS AND WALL AND CEILING PANELS IN |
| | SHOWER AREAS. WATER-RESISTANT GYPSUM BACKING BOARD |
| | SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET |
| | COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH |
| | GA-216 OR ASTM C 840 AND MANUFACTURER RECOMMENDATIONS. |
| | REGULAR GYPSUM WALLBOARD IS PERMITTED UNDER TILE OR |
| | WALL PANELS IN OTHER WALL AND CEILING AREAS WHEN |
| | INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C 840. |
| | |
| | 2509.3 LIMITATIONS. WATER-RESISTANT GYPSUM BACKING |
| | BOARD SHALL NOT BE USED IN THE FOLLOWING LOCATIONS: |
| | 1. OVER A VAPOR RETARDER IN SHOWER OR BATHTUB |
| | COMPARTMENTS. |
| | 2. WHERE THERE WILL BE DIRECT EXPOSURE TO WATER OR IN |
| | AREAS SUBJECT TO CONTINUOUS HIGH HUMIDITY. |
| | 3. ON CEILINGS WHERE FRAME SPACING EXCEEDS 12 INCHES |
| | (305 MM) O.C. FOR 1/2-INCH THICK (12.7 MM) |
| | WATER-RESISTANT GYPSUM BACKING BOARD AND MORE THAN 16 |
| | INCHES (406 MM) O.C. FOR 5/8-INCH THICK (15.9 MM) |
| | WATER-RESISTANT GYPSUM BACKING BOARD. |
| | |
| | STEVEN KENNEDY, CBO |