| 2016-09-23 14:53:46 | 1ST REVIEW |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER LL |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 561-805-6711 |
| | [email protected] |
| | |
| | PLUMBING COMMENTS |
| | |
| | 1) THE LIFE SAFETY SHEET INDICATES THIS IS A CHANGE OF |
| | OCCUPANCY DAYCARE WITH AN OCCUPANT LOAD OF 31 OCCUPANTS |
| | (20 NET). PLEASE PROVIDE THE SQUARE FOOTAGE OF THE |
| | CHANGE OF OCCUPANCY AND SEE FBC-B TABLE 10041.2 THE |
| | OCCUPANT LOAD FACTOR IS (35 NET). |
| | |
| | 2) THE CODE ANALYSIS INDICATES THE OCCUPANCY AS AN (D) |
| | DAYCARE OCCUPANCY. PLEASE INDICATE AS TO WHICH TYPE OF |
| | DAYCARE/ EDUCATIONAL FACILITY THIS USE WILL FALL INTO: |
| | 2014 FBC-B 305.2 GROUP E, DAY CARE FACILITIES. THIS |
| | GROUP INCLUDES BUILDINGS AND STRUCTURES OR PORTIONS |
| | THEREOF OCCUPIED BY MORE THAN FIVE CHILDREN OLDER THAN |
| | 2 1/2 YEARS OF AGE WHO RECEIVE EDUCATIONAL, SUPERVISION |
| | OR PERSONAL CARE SERVICES FOR FEWER THAN 24 HOURS PER |
| | DAY. |
| | OR |
| | 308.6.1 CLASSIFICATION AS GROUP E. A CHILD DAY CARE |
| | FACILITY THAT PROVIDES CARE FOR MORE THAN FIVE BUT NO |
| | MORE THAN 100 CHILDREN 2 1/2 YEARS OR LESS OF AGE, |
| | WHERE THE ROOMS IN WHICH THE CHILDREN ARE CARED FOR ARE |
| | LOCATED ON A LEVEL OF EXIT DISCHARGE SERVING SUCH ROOMS |
| | AND EACH OF THESE CHILD CARE ROOMS HAS AN EXIT DOOR |
| | DIRECTLY TO THE EXTERIOR, SHALL BE CLASSIFIED AS GROUP |
| | E. |
| | OR |
| | CHILDREN 2 1/2 YEARS OF AGE OR LESS USUALLY ARE NOT |
| | ABLE TO RECOGNIZE AN EMERGENCY SITUATION, MAY NOT |
| | RESPOND APPROPRIATELY OR MAY NOT BE ABLE TO EGRESS |
| | WITHOUT ASSISTANCE; THUS FACILITIES THAT HAVE MORE THAN |
| | 5 CHILDREN 2 1/2 YEARS OF AGE OR LESS ARE CLASSIFIED AS |
| | CHILD CARE FACILITIES AND CONSIDERED TO BE GROUP I-4. |
| | |
| | 3) THE PLAN INDICATES A PROPOSED DAYCARE CLASSROOM, IS |
| | THIS ROOM BEING ADDED TO AN EXISTING DAYCARE? THE PLANS |
| | DO NOT SHOW WHERE THE TOILET FACILITIES FOR THE |
| | DAYCARE, NOR THE FACILITIES TO BE USED FOR THE ADULTS? |
| | |
| | |
| | 4A) 468.3.5.2 TEACHER TOILETS. FACULTY AND STAFF |
| | TOILETS SHALL BE SEPARATE FROM STUDENT TOILETS. |
| | |
| | 4B) 468.3.5.5 WALLS. WALLS IN TOILET ROOMS SHALL BE |
| | IMPERVIOUS TO A HEIGHT OF AT LEAST 4 FEET (1219 MM) |
| | ABOVE THE FLOOR. WALLS IN KITCHENS, SCULLERIES, CAN |
| | WASH AREAS, AND SHOWER ROOMS SHALL BE IMPERVIOUS TO A |
| | HEIGHT OF AT LEAST 6 FEET (1829 MM) ABOVE THE FLOOR. |
| | TOILET AND SHOWER PARTITIONS SHALL BE IMPERVIOUS. |
| | |
| | 4C) 2014 FBC-ACCESS. CODE 604.1 GENERAL. WATER CLOSETS |
| | AND TOILET COMPARTMENTS SHALL COMPLY WITH 604.2 THROUGH |
| | 604.8. EXCEPTION: WATER CLOSETS AND TOILET COMPARTMENTS |
| | FOR CHILDREN?S USE SHALL BE PERMITTED TO COMPLY WITH |
| | 604.9. 604.9 WATER CLOSETS AND TOILET COMPARTMENTS FOR |
| | CHILDREN?S USE. |
| | |
| | 4D) WATER CLOSETS AND TOILET COMPARTMENTS FOR |
| | CHILDREN?S USE SHALL COMPLY WITH 604.9. |
| | |
| | 4E) 468.3.4 DIAPER CHANGING STATIONS. A DIAPER CHANGING |
| | STATION SHALL BE LOCATED IN OR ADJACENT TO ANY |
| | CLASSROOM WHERE CHILDREN WEARING DIAPERS ARE IN |
| | ATTENDANCE. A HAND WASHING LAVATORY SHALL BE PROVIDED |
| | WITHIN THE CHANGING STATION AREA. ACCESS SHALL BE |
| | PROVIDED TO THE LAVATORY WITHOUT OPENING DOORS OR |
| | TOUCHING A HANDLE. |
| | |
| | 5) PLEASE INDICATE PREVIOUS OCCUPANCY USE. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 6) PROVIDE A FLOOR PLAN CLEARLY SHOWING ALL PLUMBING |
| | FIXTURES . PER WPB AMEND TO FBC 107.2.1 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |