| 2016-09-09 11:33:58 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | PROJECT NAME: SUNFLOWER LEARNING CENTER. |
| | JOB ADDRESS: 2727 GEORGIA AVE. |
| | DESCRIPTION: CHANGE OF USE |
| | MASTER PERMIT: 16081168 |
| | |
| | BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS. |
| | ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF |
| | SUBMITTED CORRECTIONS. |
| | |
| | 1. BEFORE A PROPER ELECTRICAL REVIEW CAN BE CONDUCTED I |
| | NEED TO KNOW AND IT SHOULD BE INDICATED ON THE PLANS |
| | THE CURRENT GROUP AND CLASSIFICATION OF THE AREA IN |
| | QUESTION ALONG WITH THE NEW GROUP AND CLASSIFICATION. |
| | 2. DEPENDING ON THE ABOVE, A CHANGE IN FIRE ALARM |
| | SYSTEM MAY BE REQUIRED. IF SO, THE FIRE ALARM WORK |
| | SHALL BE SUBMITTED UNDER A SEPARATE PERMIT AND PLANS |
| | SUBMITTAL. |
| | 3. INCLUDE ON THE PLANS ANY FIRE SEPARATIONS APPLICABLE |
| | TO THE AREA IN QUESTION. |
| | 4. ADDITIONAL CORRECTIONS MAY BE REQUIRED ONCE THE |
| | PLANS AS DESCRIBED ABOVE ARE SUBMITTED. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |
| | |