| 2016-08-30 06:27:22 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16081161 |
| | ADD: 3300 BROADWAY |
| | CONT: GULFSTREAM ROOFING |
| | TEL: 786-357-5327 |
| | E-MAIL: ??????? NOT GIVEN/ WE COMMUNICATE BY E-MAIL |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. AUGUST 30/2016 |
| | ACTION: DENIED |
| | |
| | 1) THE PRODUCT APPROVAL SUBMITTED IS 13-1022.15/ GAF |
| | CONVENTIONAL BUILT-UP ROOF SYSTEM FOR WOOD DECKS. 16 |
| | PAGES. PLEASE NOTE THE WRITE UP FROM A+ENGINEERING |
| | TESTING LABS INDICATES THE NOA : 14-1030.02 SUBSYSTEM |
| | PAGES 26& 27. THE WRONG PRODUCT APPROVAL SUBMITTED OR |
| | THE WRONG ENGINEERING SUBMITTED? 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE |
| | CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND |
| | DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS, |
| | FASTENING REQUIREMENTS, FLASHING REQUIREMENTS AND WIND |
| | RESISTANCE RATING THAT ARE REQUIRED TO BE INSTALLED. |
| | PRODUCT EVALUATION AND INSTALLATION SHALL INDICATE |
| | COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR THE |
| | SPECIFIC SITE OR A STATEMENT BY AN ARCHITECT OR |
| | ENGINEER FOR THE SPECIFIC SITE MUST BE SUBMITTED WITH |
| | THE CONSTRUCTION DOCUMENTS. |
| | |