| 2016-08-31 11:44:24 | BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 16081158 |
| | W. P. B. PERMIT: 16061143 |
| | ADD: 429 25TH ST. |
| | CONT: LUCAS CONSTRUCTION |
| | TEL: 772-423-3892 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. AUG. 31/2016 |
| | ACTION: DENIED |
| | |
| | 1)THE PLANS SHEET A-1 INDICATE THE PRODUCTS CERTAINTEED |
| | MODIFIED BITUMEN TORCH DOWN APPLIED CONCRETE T-SECTIONS |
| | AT ROOF OVERHANG ONLY, SUBMITTED GAF RUBEROID MODIFIED |
| | BITUMEN. NOT THE PRODUCT SPECIFIED ON THE SHEET A-1. |
| | DISCREPANCY IN THE PLANS AND SUBMITTED |
| | PRODUCT.107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 2) SHEET A-1 ALSO IDENTIFIED A 2ND ROOFING PRODUCT AND |
| | APPLICATION, CERTAINTEED MODIFIED BITUMEN TORCH APPLIED |
| | ROOF, APPLIED TO NEW PRE-PRIMED DENSGLASS DECKING |
| | MECHANICALLY FASTENED TO THE EXISTING METAL DECK AT |
| | CIRCULAR OVERHANG ONLY. THIS PRODUCT NEVER WAS |
| | SUBMITTED. IF THE DENSGLASS IS BEING REPLACED THEN |
| | PRODUCT INFORMATION WILL ALSO BE REQUIRED. |
| | |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(D) ROOFING PRODUCTS AND ASSEMBLIES. |
| | |
| | 2B) FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL |
| | ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR |
| | ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, |
| | IF ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3. |
| | FASTENER DENSITIES SHALL BE INCREASED FOR BOTH |
| | INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE |
| | WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION |
| | PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED |
| | PROFESSIONAL ENGINEER OR REGISTERED ARCHITECT. |
| | |
| | 3) CLOSING |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |