Plan Review Notes
Plan Review Notes For Permit 16081110
Permit Number 16081110
Review Stop M
Sequence Number 5
Notes
Date Text
2018-01-19 17:25:54RESIDENTIAL (R3) ADDITION/ALTERATION FIFTH MECHANICAL
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
  
 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS (2
 COPIES) AS REQUIRED BY SEC. R403.6.1 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
 NOTE: ONLY THE SUMMARY SHEET WAS SUBMITTED. NEED TO
 PROVIDE COMPLETE CALCULATIONS.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
  
 2- THE EQUIPMENT LISTED IN THE CALCULATIONS SUBMITTED
 DOESN'T COMPLY WITH SEC. R403.6.1.1 FBC-ENERGY
 CONSERVATION. "THE CORRESPONDING LATENT CAPACITY OF THE
 EQUIPMENT SHALL NOT BE LESS THAN THE CALCULATED LATENT
 LOAD". REVISE EQUIPMENT AS REQUIRED.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
  
 3- EQUIPMENT CALCULATIONS SUBMITTED ARE MISSING THE
 PUBLISHED AHRI REFERENCE. SEC.R403.6.1.1 FBC-ENERGY
 CONSERVATION. PROVIDE THE AHRI NUMBER.
  
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]