| 2017-11-20 12:40:30 | RESIDENTIAL (R3) ADDITION/ALTERATION FOURTH BUILDING |
| | REVIEW CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | |
| | NOTE: |
| | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| | MEANS THAT CONTRACTOR WILL SUBMIT REQUIRED INFORMATION |
| | PRIOR TO INSPECTIONS TO AVOID CONFLICTS/DELAYS. |
| | REVISION FEES MAY APPLY. CONTRACTOR TO ADVICE IF THE |
| | PROVISO OPTION IS PREFERRED AT THIS TIME. NEED TO HAVE |
| | THE ENERGY CALCULATIONS CERTIFIED BY THE OWNER OF |
| | LEGALLY DESIGNATED AGENT AND BUILDER NEEDS TO COMPLETE |
| | THE EPL DISPLAY CARD BEFORE ISSUING PERMIT. |
| | |
| | |
| | 1- ENERGY CALCULATIONS FORM R405-2014 SUBMITTED: |
| | A) OWNER OR LEGALLY DESIGNATED AGENT SHALL CERTIFY AT |
| | THE BOTTOM OF FORM SUBMITTED AS REQUIRED BY SEC. |
| | R103.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | |
| | B) BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL |
| | (EPL) DISPLAY CARD ENCLOSED IN THE ENERGY CALCULATIONS |
| | PACKAGE. SEC. R405.4.3 FBC-ENERGY CONSERVATION. |
| | |
| | 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS (DOORS, |
| | WINDOWS AND ROOFING) AS REQUIRED BY SEC. 107.3.4.1 CITY |
| | AMENDMENTS. |
| | |
| | 3- FLAT ROOF NOA 14-1030.02 SUBMITTED: |
| | A) CLEARLY MARK SPECIFIC APPROVED ASSEMBLY TO BE |
| | INSTALLED TO VERIFY COMPLIANCE WIT THE DESIGN PRESSURES |
| | OF SEC. R301.1 FBC-RESIDENTIAL. |
| | RESPONSE: REPEAT COMMENT. |
| | |
| | B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS (2 |
| | COPIES) AS REQUIRED BY GENERAL LIMITATION # 7 ON LAST |
| | PAGE OF NOA SUBMITTED. REQUIRED TO MEET THE DESIGN |
| | PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. |
| | RESPONSE: REPEAT COMMENT. |
| | |
| | 4- REVISE SURVEY DRAWN ON 08/06/17. ACCORDING TO FLOOD |
| | INSURANCE RATE MAP (FIRM) COMMUNITY PANEL NUMBER 120229 |
| | 0020B EFFECTIVE DATE MARCH 1, 1979 THIS BUILDING IS |
| | LOCATED IN FLOOD ZONE "C" NOT "B". REVISE AS REQUIRED. |
| | SEC. R107.2.1 AND SEC. 107.2.5 CITY AMENDMENTS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |