| Plan Review Notes For Permit 16081110 |
| Permit Number |
16081110 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2017-06-29 16:33:28 | RESIDENTIAL (R3) ADDITION/ALTERATION THIRD MECHANICAL | | | REVIEW CHECKLIST. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS (2 | | | COPIES) AS REQUIRED BY SEC. R403.6.1 FBC-ENERGY | | | CONSERVATION, 5TH EDITION (2014). | | | NOTE: ONLY THE SUMMARY SHEET WAS SUBMITTED. NEED TO | | | PROVIDE COMPLETE CALCULATIONS. | | | | | | 2- THE EQUIPMENT LISTED IN THE CALCULATIONS SUBMITTED | | | DOESN'T COMPLY WITH SEC. R403.6.1.1 FBC-ENERGY | | | CONSERVATION. "THE CORRESPONDING LATENT CAPACITY OF THE | | | EQUIPMENT SHALL NOT BE LESS THAN THE CALCULATED LATENT | | | LOAD". REVISE EQUIPMENT AS REQUIRED. | | | | | | 3- EQUIPMENT CALCULATIONS SUBMITTED ARE MISSING THE | | | PUBLISHED AHRI REFERENCE. SEC.R403.6.1.1 FBC-ENERGY | | | CONSERVATION. PROVIDE THE AHRI NUMBER. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|