| 2017-06-28 17:32:34 | RESIDENTIAL (R3) ADDITION/ALTERATION THIRD BUILDING |
| | REVIEW CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | NOTE: |
| | ENGINEER OF RECORD MAY BE CHARGED FOUR TIMES THE PLAN |
| | REVIEW FEE AS REQUIRED BY FLORIDA STATUTE 553.80(2)(B) |
| | FOR MULTIPLE PLAN REVIEW REJECTIONS. |
| | |
| | |
| | 1- NEW ENERGY CALCULATIONS FORM R405-2014 SUBMITTED: |
| | A) OWNER OR LEGALLY DESIGNATED AGENT SHALL CERTIFY AT |
| | THE BOTTOM OF FORM SUBMITTED AS REQUIRED BY SEC. |
| | R103.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | |
| | B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| | INCLUDING OWNER NAME, BUILDER NAME, PERMIT OFFICE AND |
| | JURISDICTION. SEC. R101.5.1.1.2 FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). |
| | |
| | C) ITEM #9: PERSON PREPARING THE ENERGY CALCULATIONS TO |
| | IDENTIFY WHERE ARE THE CONCRETE BLOCK WALLS WITH R5 |
| | INSULATION AND R4.1 INSULATION. ALSO, THE ARE DOESN'T |
| | MATCH AREA SHOWN ON PLANS. SEE PLANS AND REVISE AS |
| | REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | D) REVISE CEILING INSULATION SPECIFIED ON ITEM #10. THE |
| | R30 BATT INSULATION DOESN'T FIT ON 2X8 ROOF JOISTS. |
| | COORDINATE WITH ENGINEER'S REVISE PLANS AND REVISE AS |
| | REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | E) REVISE THE ROOF TYPE AND ROOF MATERIALS SPECIFIED ON |
| | PAGE 2 OF 4 TO MATCH PLANS. THE ADDITION IS A FLAT |
| | ROOF. |
| | |
| | F) REVISE THE ORIENTATION OF THE WALLS SHOWN ON PAGE 3 |
| | OF 4 TO MATCH PLANS. THERE ARE NO WALL ON THE WEST |
| | SIDE. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | G) REVISE THE ORIENTATION OF THE DOOR SHOWN ON PAGE 3 |
| | OF 4 TO MATCH PLANS. THERE ARE NO DOORS ON THE WEST |
| | SIDE. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | H) REVISE THE ORIENTATION OF THE WINDOW SHOWN ON PAGE 3 |
| | OF 4 TO MATCH PLANS. THERE ARE NO WINDOWS ON THE WEST |
| | SIDE. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | I) BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL |
| | (EPL) DISPLAY CARD ENCLOSED IN THE ENERGY CALCULATIONS |
| | PACKAGE. SEC. R405.4.3 FBC-ENERGY CONSERVATION. |
| | |
| | 2- REVISE ROOF SLOPE SHOWN ON THE EXTERIOR ELEVATIONS. |
| | THE REQUIRED SLOPE IS 1/4" PER FT MIN. SEC. R905.9 |
| | FBC-RESIDENTIAL. |
| | RESPONSE: REPEAT COMMENT. |
| | |
| | 3- TYPICAL WALL SECTION ON SHEET A-1: |
| | A) NEED TO PROVIDE ROOF CROSS VENTILATION AS REQUIRED |
| | BY SEC. R806 FBC-RESIDENTIAL. SPECIFIED VENTS DON'T |
| | PROVIDE CROSS VENTILATION ON A FLAT ROOF WITH SOLID 2X8 |
| | ROOF JOISTS. REVISE AS REQUIRED. |
| | RESPONSE: REPEAT COMMENT. |
| | NOTE: |
| | ENGINEER OF RECORD MAY BE CHARGED FOUR TIMES THE PLAN |
| | REVIEW FEE AS REQUIRED BY FLORIDA STATUTE 553.80(2)(B) |
| | FOR MULTIPLE PLAN REVIEW REJECTIONS. |
| | |
| | B) R-30 BATT INSULATION IS 9-1/2" THICK. IT DOESN'T FIT |
| | ON 2 X 8 ROOF JOISTS. IN ADDITION R-30 INSULATION |
| | DOESN'T ALLOW FOR THE 1" VENTILATION CLEARANCE AS |
| | REQUIRED BY SEC. R806.3 FBC-RESIDENTIAL. REVISE AS |
| | REQUIRED. |
| | RESPONSE: REPEAT COMMENT. |
| | NOTE: |
| | ENGINEER OF RECORD MAY BE CHARGED FOUR TIMES THE PLAN |
| | REVIEW FEE AS REQUIRED BY FLORIDA STATUTE 553.80(2)(B) |
| | FOR MULTIPLE PLAN REVIEW REJECTIONS. |
| | |
| | C) THE OVERHANG DIMENSION DOESN'T MATCH OVERHANG |
| | DIMENSION SHOWN ON THE ROOF FRAMING PLAN. REVISE AS |
| | REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) SINGLE HUNG WINDOWS AS SHOWN ON PLANS. DWGS NO |
| | 08-02476 SUBMITTED DON'T HAVE A FLORIDA PRODUCT |
| | APPROVAL NUMBER OR MIAMI-DADE NOA NUMBER. PROVIDE |
| | FLORIDA OR MIAMI-DADE COVER PAGE THAT CORRESPONDS TO |
| | DRAWINGS SUBMITTED. IF THERE IS NOT CURRENT FLORIDA OR |
| | MIAMI-DADE APPROVAL, THEN MANUFACTURER MAY APPLY FOR |
| | LOCAL PRODUCT APPROVAL BY SUBMITTING COMPLETE ORIGINAL |
| | ENGINEER PACKAGE FOR BUILDING OFFICIAL APPROVAL. ADVICE |
| | IF APPLYING FOR LOCAL PRODUCT APPROVAL FOR FURTHER |
| | INSTRUCTIONS. |
| | RESPONSE: REPEAT COMMENT. PROVIDE FLORIDA PRODUCT |
| | APPROVAL COVER PAGE THAT CORRESPOND TO DRAWINGS |
| | SUBMITTED. |
| | |
| | B) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| | RESPONSE: REPEAT COMMENT. |
| | |
| | C) SIMPSON STRUCTURAL CONNECTORS AS SPECIFIED ON PLANS. |
| | PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL COVER PAGE |
| | AND PAGE SHOWING THE SPECIFIED CONNECTOR OR ENGINEER TO |
| | LIST THE FLORIDA PRODUCT APPROVAL NEXT TO EACH |
| | SPECIFIED CONNECTOR. |
| | RESPONSE: REPEAT COMMENT. |
| | |
| | 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS (DOORS, |
| | WINDOWS AND ROOFING) AS REQUIRED BY SEC. 107.3.4.1 CITY |
| | AMENDMENTS. |
| | RESPONSE: REPEAT COMMENT. |
| | |
| | 6- FLAT ROOF NOA 14-1030.02 SUBMITTED: |
| | A) CLEARLY MARK SPECIFIC APPROVED ASSEMBLY TO BE |
| | INSTALLED TO VERIFY COMPLIANCE WIT THE DESIGN PRESSURES |
| | OF SEC. R301.1 FBC-RESIDENTIAL. |
| | RESPONSE: REPEAT COMMENT. |
| | |
| | B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS (2 |
| | COPIES) AS REQUIRED BY GENERAL LIMITATION # 7 ON LAST |
| | PAGE OF NOA SUBMITTED. REQUIRED TO MEET THE DESIGN |
| | PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. |
| | RESPONSE: REPEAT COMMENT. |
| | |
| | 7- ROOF FRAMING PLAN: SPECIFY HOW ARE THE ROOF JOISTS |
| | CONNECTED TO THE "EXISTING CONCRETE BEAM". SEC. R301.1 |
| | FBC-RESIDENTIAL. |
| | RESPONSE: REPEAT COMMENT. |
| | NOTE: |
| | ENGINEER OF RECORD MAY BE CHARGED FOUR TIMES THE PLAN |
| | REVIEW FEE AS REQUIRED BY FLORIDA STATUTE 553.80(2)(B) |
| | FOR MULTIPLE PLAN REVIEW REJECTIONS. |
| | |
| | 8- THE SCOPE OF WORK IS NOT ALTERATION LEVEL 2. REVISE |
| | INFORMATION AT THE BOTTOM RIGHT OF SHEET A-1. THIS IS |
| | AN ADDITION. SEC. 507 FBC-EXISTING BUILDING, 5TH |
| | EDITION (2014). |
| | RESPONSE: REPEAT COMMENT. |
| | |
| | ****ENGINEER OF RECORD TO PROVIDE RESPONSE LETTER |
| | ADDRESSING EACH COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |