Plan Review Notes
Plan Review Notes For Permit 16081110
Permit Number 16081110
Review Stop B
Sequence Number 3
Notes
Date Text
2017-06-28 17:32:34RESIDENTIAL (R3) ADDITION/ALTERATION THIRD BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 ENGINEER OF RECORD MAY BE CHARGED FOUR TIMES THE PLAN
 REVIEW FEE AS REQUIRED BY FLORIDA STATUTE 553.80(2)(B)
 FOR MULTIPLE PLAN REVIEW REJECTIONS.
  
  
 1- NEW ENERGY CALCULATIONS FORM R405-2014 SUBMITTED:
 A) OWNER OR LEGALLY DESIGNATED AGENT SHALL CERTIFY AT
 THE BOTTOM OF FORM SUBMITTED AS REQUIRED BY SEC.
 R103.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER NAME, BUILDER NAME, PERMIT OFFICE AND
 JURISDICTION. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 C) ITEM #9: PERSON PREPARING THE ENERGY CALCULATIONS TO
 IDENTIFY WHERE ARE THE CONCRETE BLOCK WALLS WITH R5
 INSULATION AND R4.1 INSULATION. ALSO, THE ARE DOESN'T
 MATCH AREA SHOWN ON PLANS. SEE PLANS AND REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D) REVISE CEILING INSULATION SPECIFIED ON ITEM #10. THE
 R30 BATT INSULATION DOESN'T FIT ON 2X8 ROOF JOISTS.
 COORDINATE WITH ENGINEER'S REVISE PLANS AND REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 E) REVISE THE ROOF TYPE AND ROOF MATERIALS SPECIFIED ON
 PAGE 2 OF 4 TO MATCH PLANS. THE ADDITION IS A FLAT
 ROOF.
  
 F) REVISE THE ORIENTATION OF THE WALLS SHOWN ON PAGE 3
 OF 4 TO MATCH PLANS. THERE ARE NO WALL ON THE WEST
 SIDE. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 G) REVISE THE ORIENTATION OF THE DOOR SHOWN ON PAGE 3
 OF 4 TO MATCH PLANS. THERE ARE NO DOORS ON THE WEST
 SIDE. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 H) REVISE THE ORIENTATION OF THE WINDOW SHOWN ON PAGE 3
 OF 4 TO MATCH PLANS. THERE ARE NO WINDOWS ON THE WEST
 SIDE. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 I) BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD ENCLOSED IN THE ENERGY CALCULATIONS
 PACKAGE. SEC. R405.4.3 FBC-ENERGY CONSERVATION.
  
 2- REVISE ROOF SLOPE SHOWN ON THE EXTERIOR ELEVATIONS.
 THE REQUIRED SLOPE IS 1/4" PER FT MIN. SEC. R905.9
 FBC-RESIDENTIAL.
 RESPONSE: REPEAT COMMENT.
  
 3- TYPICAL WALL SECTION ON SHEET A-1:
 A) NEED TO PROVIDE ROOF CROSS VENTILATION AS REQUIRED
 BY SEC. R806 FBC-RESIDENTIAL. SPECIFIED VENTS DON'T
 PROVIDE CROSS VENTILATION ON A FLAT ROOF WITH SOLID 2X8
 ROOF JOISTS. REVISE AS REQUIRED.
 RESPONSE: REPEAT COMMENT.
 NOTE:
 ENGINEER OF RECORD MAY BE CHARGED FOUR TIMES THE PLAN
 REVIEW FEE AS REQUIRED BY FLORIDA STATUTE 553.80(2)(B)
 FOR MULTIPLE PLAN REVIEW REJECTIONS.
  
 B) R-30 BATT INSULATION IS 9-1/2" THICK. IT DOESN'T FIT
 ON 2 X 8 ROOF JOISTS. IN ADDITION R-30 INSULATION
 DOESN'T ALLOW FOR THE 1" VENTILATION CLEARANCE AS
 REQUIRED BY SEC. R806.3 FBC-RESIDENTIAL. REVISE AS
 REQUIRED.
 RESPONSE: REPEAT COMMENT.
 NOTE:
 ENGINEER OF RECORD MAY BE CHARGED FOUR TIMES THE PLAN
 REVIEW FEE AS REQUIRED BY FLORIDA STATUTE 553.80(2)(B)
 FOR MULTIPLE PLAN REVIEW REJECTIONS.
  
 C) THE OVERHANG DIMENSION DOESN'T MATCH OVERHANG
 DIMENSION SHOWN ON THE ROOF FRAMING PLAN. REVISE AS
 REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) SINGLE HUNG WINDOWS AS SHOWN ON PLANS. DWGS NO
 08-02476 SUBMITTED DON'T HAVE A FLORIDA PRODUCT
 APPROVAL NUMBER OR MIAMI-DADE NOA NUMBER. PROVIDE
 FLORIDA OR MIAMI-DADE COVER PAGE THAT CORRESPONDS TO
 DRAWINGS SUBMITTED. IF THERE IS NOT CURRENT FLORIDA OR
 MIAMI-DADE APPROVAL, THEN MANUFACTURER MAY APPLY FOR
 LOCAL PRODUCT APPROVAL BY SUBMITTING COMPLETE ORIGINAL
 ENGINEER PACKAGE FOR BUILDING OFFICIAL APPROVAL. ADVICE
 IF APPLYING FOR LOCAL PRODUCT APPROVAL FOR FURTHER
 INSTRUCTIONS.
 RESPONSE: REPEAT COMMENT. PROVIDE FLORIDA PRODUCT
 APPROVAL COVER PAGE THAT CORRESPOND TO DRAWINGS
 SUBMITTED.
  
 B) PRECAST LINTELS AS SPECIFIED ON PLANS.
 RESPONSE: REPEAT COMMENT.
  
 C) SIMPSON STRUCTURAL CONNECTORS AS SPECIFIED ON PLANS.
 PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL COVER PAGE
 AND PAGE SHOWING THE SPECIFIED CONNECTOR OR ENGINEER TO
 LIST THE FLORIDA PRODUCT APPROVAL NEXT TO EACH
 SPECIFIED CONNECTOR.
 RESPONSE: REPEAT COMMENT.
  
 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS (DOORS,
 WINDOWS AND ROOFING) AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
 RESPONSE: REPEAT COMMENT.
  
 6- FLAT ROOF NOA 14-1030.02 SUBMITTED:
 A) CLEARLY MARK SPECIFIC APPROVED ASSEMBLY TO BE
 INSTALLED TO VERIFY COMPLIANCE WIT THE DESIGN PRESSURES
 OF SEC. R301.1 FBC-RESIDENTIAL.
 RESPONSE: REPEAT COMMENT.
  
 B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS (2
 COPIES) AS REQUIRED BY GENERAL LIMITATION # 7 ON LAST
 PAGE OF NOA SUBMITTED. REQUIRED TO MEET THE DESIGN
 PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 RESPONSE: REPEAT COMMENT.
  
 7- ROOF FRAMING PLAN: SPECIFY HOW ARE THE ROOF JOISTS
 CONNECTED TO THE "EXISTING CONCRETE BEAM". SEC. R301.1
 FBC-RESIDENTIAL.
 RESPONSE: REPEAT COMMENT.
 NOTE:
 ENGINEER OF RECORD MAY BE CHARGED FOUR TIMES THE PLAN
 REVIEW FEE AS REQUIRED BY FLORIDA STATUTE 553.80(2)(B)
 FOR MULTIPLE PLAN REVIEW REJECTIONS.
  
 8- THE SCOPE OF WORK IS NOT ALTERATION LEVEL 2. REVISE
 INFORMATION AT THE BOTTOM RIGHT OF SHEET A-1. THIS IS
 AN ADDITION. SEC. 507 FBC-EXISTING BUILDING, 5TH
 EDITION (2014).
 RESPONSE: REPEAT COMMENT.
  
 ****ENGINEER OF RECORD TO PROVIDE RESPONSE LETTER
 ADDRESSING EACH COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]