| Date |
Text |
| 2017-02-14 17:52:33 | |
| | 05/24/17 MET W/ CONTRACTOR (JUNIOR) TO GO OVER |
| | COMMENTS. EXISTING ADDITION IN QUESTION WAS CLARIFIED. |
| | IT WAS BUILT LONG TIME AGO AND SHOWN ON THE GREEN CARD. |
| | JG. |
| | |
| | |
| | RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING |
| | REVIEW CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | NOTE: |
| | THERE IS A CONFLICT WITH PERMIT #14100767 AND PLANS |
| | SUBMITTED NOW FOR THE BEDROOM ADDITION. PERMIT |
| | #14100767 WAS FOR AN STORAGE ROOM. PLANS SUBMITTED NOW |
| | INDICATE THAT THIS AREA IS LIVABLE AREA (NO STORAGE). |
| | IN 2014 PERMIT APPLICATION AND PLANS WERE SUBMITTED TO |
| | RE-OPEN EXPIRED PERMIT #99120889. PERMIT #14100767 WAS |
| | NEVER ISSUED. IT WAS ABANDONED. NEED TO INVESTIGATE IF |
| | THE WORK WAS DONE. THERE ARE NO PERMITS OR INSPECTIONS |
| | FOR THE WORK IN THIS AREA. FEES FOR WORK WITHOUT PERMIT |
| | MAY APPLY. |
| | |
| | |
| | 1- BASED ON THE PRESCRIPTIVE ENERGY CALCULATIONS FORM |
| | R402-2014 SUBMITTED THE FOLLOWING ITEMS ARE REQUIRED: |
| | A) CONCRETE BLOCK WALL TO HAVE INSULATION ON THE |
| | INTERIOR AND EXTERIOR SIDE OF THE WALL. SEE TABLE R402A |
| | OF FORM R402-2014 SUBMITTED. ENGINEER OF RECORD TO |
| | PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING HOW |
| | THE INSULATION IS GOING TO BE INSTALLED ON BOTH SIDES |
| | OF THE WALL. SEC. R103.2 FBC-ENERGY CONSERVATION. |
| | |
| | B) NEED R-30 CEILING INSULATION. SEE TABLE R402A FOR |
| | MANDATORY REQUIREMENTS. R-30 BATT INSULATION DOESN'T |
| | FIT ON 2X8 ROOF JOISTS. R-30 BATT INSULATION IS ABOUT |
| | 9-1/2" THICK. ALSO, NEED AT LEAST 1" CLEARANCE BETWEEN |
| | THE INSULATION AND THE ROOF SHEATHING FOR ROOF |
| | VENTILATION AS REQUIRED BY SEC. R806.3 FBC-RESIDENTIAL. |
| | REVISE PLANS AS REQUIRED. |
| | |
| | |
| | 2- ENERGY CALCULATIONS PRESCRIPTIVE FORM R402-2014 |
| | SUBMITTED: (NOTE: IF ITEMS REQUIRED BY TABLE R402A CAN |
| | NOT BE INSTALLED, THEN THIS PRESCRIPTIVE METHOD CAN NOT |
| | BE USED). |
| | A) CALCULATIONS NEED TO BE CERTIFIED AND DATED BY THE |
| | OWNER AT THE BOTTOM OF FORM AS REQUIRED BY SEC. |
| | R103.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | |
| | B) PROVIDE THE NAME OF THE PERSON WHO PREPARED THE |
| | ENERGY CALCULATIONS AND DATE IT WAS SIGNED AS REQUIRED |
| | BY SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | C) COMPLETE WINDOWS ITEM # 6(A) AND #6(B) AS REQUIRED |
| | BY SEC. R101.5.1.1.1 FBC-ENERGY CONSERVATION, 5TH |
| | EDITION (2014). NOTE: SEE TABLE R402A FOR MANDATORY |
| | REQUIREMENTS. |
| | |
| | D) COMPLETE FLOOR ITEM #8 AS REQUIRED BY SEC. |
| | R101.5.1.1.1 FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). NOTE: SEE TABLE R402A FOR MANDATORY |
| | REQUIREMENTS. |
| | |
| | E) COMPLETE WALL ITEM #9 AS REQUIRED BY SEC. |
| | R101.5.1.1.1 FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). NOTE: NEED INSULATION ON THE INTERIOR SIDE AND |
| | EXTERIOR SIDE OF THE CONCRETE BLOCK WALL. SEE TABLE |
| | R402A FOR MANDATORY REQUIREMENTS. |
| | |
| | F) COORDINATE CEILING R-VALUE ON ITEM #10 WITH REVISED |
| | INFORMATION REQUIRED BY ITEM #1(B) ABOVE. NOTE: IF R-30 |
| | INSULATION CAN NOT BE INSTALLED, THEN THE PRESCRIPTIVE |
| | ENERGY CALCULATIONS FORM R402-2014 CAN NOT BE USED. |
| | SEC. R101.5.1.1.1 FBC-ENERGY CONSERVATION. |
| | |
| | G) COMPLETE ALL THE INFORMATION ON COOLING SYSTEM ITEM |
| | #12 (A) AND (B) AS REQUIRED BY SEC. R101.5.1.1.1 |
| | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | |
| | H) COMPLETE ALL THE INFORMATION ON HEATING SYSTEM ITEM |
| | #13 (A) AND (B) AS REQUIRED BY SEC. R101.5.1.1.1 |
| | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | |
| | I) COMPLETE ALL THE INFORMATION HVAC SIZING |
| | CALCULATIONS ON ITEM # 14 AS REQUIRED BY SEC. |
| | R101.5.1.1.1 FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | |
| | J) COMPLETE ALL THE INFORMATION ON WATER HEATING SYSTEM |
| | ITEM #15 AS REQUIRED BY SEC. R101.5.1.1.1 FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). |
| | |
| | K) COMPLETE ALL THE INFORMATION ON TABLES R402A AND |
| | TABLE R402B AS REQUIRED BY SEC. R101.5.1.1.1 FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). |
| | |
| | L) BASED ON PLANS SUBMITTED, IT LOOKS LIKE THERE IS A |
| | LIVABLE AREA ADJACENT TO THE PROPOSED ADDITION. THIS |
| | AREA WAS NOT PERMITTED AND INSPECTED. COORDINATE WITH |
| | INTRODUCTORY NOTE ON TOP OF THIS SHEET AND ITEM #3 |
| | BELOW. ENERGY CALCULATIONS NEED TO BE REVISED TO |
| | INCLUDE THE ADJACENT ROOM. SEC. R101.5.1.1.1 FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). |
| | |
| | NOTE: |
| | LABEL FOR DOORS AND WINDOWS SHOWING THE U-FACTOR AND |
| | SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS WILL |
| | BE REQUIRED FOR INSPECTION. |
| | |
| | |
| | 3- THE WEST WALL IS BLOCKED TO ALLOW FOR THE PROPOSED |
| | ADDITION. CLEARLY IDENTIFY ON PLANS THE ROOM (OR ROOMS) |
| | THAT ARE ADJACENT TO THE PROPOSED ADDITION. IF THERE IS |
| | ANY BEDROOM LOCATED ADJACENT TO THE PROPOSED ADDITION, |
| | THEN COMPLIANCE WITH THE EGRESS REQUIREMENTS NEED TO BE |
| | PROVIDED. SEC. R310 FBC-RESIDENTIAL, 5TH EDITION |
| | (2014). |
| | RESPONSE: AREA ADJACENT TO THE PROPOSED ADDITION IS |
| | SUPPOSED TO BE STORAGE NOT LIVABLE AREA. (SEE |
| | INTRODUCTORY NOTE ON TOP OF THIS SHEET REGARDING |
| | CONFLICT WITH ABANDONED PERMITS). NEED TO PROVIDE |
| | COMPLETE PLANS/DETAILS/ SPECIFICATIONS AND PRODUCT |
| | APPROVALS FOR THE AREA ADJACENT TO THE PROPOSED |
| | ADDITION. ADDITIONAL COMMENTS MAY ARISE BASED ON THE |
| | INFORMATION SUBMITTED AND VALUATION NEED TO BE UPDATED |
| | AS WELL TO INCLUDE THE ADDITONAL SCOPE OF WORK. |
| | |
| | 4- REVISE ROOF SLOPE SHOWN ON THE EXTERIOR ELEVATIONS. |
| | THE REQUIRED SLOPE IS 1/4" PER FT MIN. SEC. R905.9 |
| | FBC-RESIDENTIAL. |
| | RESPONSE: REPEAT COMMENT. |
| | |
| | 5- TYPICAL WALL SECTION ON SHEET A-1: |
| | A) NEED TO PROVIDE ROOF CROSS VENTILATION AS REQUIRED |
| | BY SEC. R806 FBC-RESIDENTIAL. SPECIFIED VENTS DON'T |
| | PROVIDE CROSS VENTILATION ON THE TYPE OF PROPOSED ROOF |
| | (FLAT). NOTE: THE 2"X8" BRACING SHOWN ON THE ROOF |
| | FRAMING PLAN IS ALSO BLOCKING THE CROSS VENTILATION. |
| | NEED TO PROVIDE AT LEAST 1" VENT AND INSULATION |
| | CLEARANCE AS REQUIRED BY SEC. R806.3 FBC-RESIDENTIAL. |
| | RESPONSE: REPEAT COMMENT. SPECIFIED VENTS DON'T PROVIDE |
| | CROSS VENTILATION. THEY ONLY PROVIDE VENTILATION WHERE |
| | THE VENT IS LOCATED. THIS TYPE OF ROOF NEEDS CONTINUOUS |
| | VENT. ALSO, R-30 BATT INSULATION IS 9-1/2" THICK. IT |
| | DOESN'T FIT ON 2 X 8 ROOF JOISTS. IN ADDITION R-30 |
| | INSULATION DOESN'T ALLOW FOR THE 1" VENT INSULATION |
| | CLEARANCE. REVISE AS REQUIRED. COORDINATE WITH THE |
| | REQUIRED REVISED ENERGY CALCULATIONS AND ITEM #1(B) |
| | ABOVE. |
| | |
| | B) SPECIFY THE WALL INSULATION. NOTE: COORDINATE WITH |
| | THE ENERGY CALCULATIONS AND COMMENT # 1(A) ABOVE. SEC. |
| | R103.2 FBC-ENERGY CONSERVATION. |
| | |
| | 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) SINGLE HUNG WINDOWS AS SHOWN ON PLANS. DWGS NO |
| | 08-02476 SUBMITTED DON'T HAVE A FLORIDA PRODUCT |
| | APPROVAL NUMBER OR MIAMI-DADE NOA NUMBER. PROVIDE |
| | FLORIDA OR MIAMI-DADE COVER PAGE THAT CORRESPONDS TO |
| | DRAWINGS SUBMITTED. IF THERE IS NOT CURRENT FLORIDA OR |
| | MIAMI-DADE APPROVAL, THEN MANUFACTURER MAY APPLY FOR |
| | LOCAL PRODUCT APPROVAL BY SUBMITTING COMPLETE ORIGINAL |
| | ENGINEER PACKAGE FOR BUILDING OFFICIAL APPROVAL. ADVICE |
| | IF APPLYING FOR LOCAL PRODUCT APPROVAL FOR FURTHER |
| | INSTRUCTIONS. |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. PROVIDE |
| | FLORIDA PRODUCT APPROVAL COVER PAGE THAT CORRESPOND TO |
| | DRAWINGS SUBMITTED. |
| | |
| | B) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | C) SIMPSON STRUCTURAL CONNECTORS AS SPECIFIED ON PLANS. |
| | PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL COVER PAGE |
| | AND PAGE SHOWING THE SPECIFIED CONNECTOR OR ENGINEER TO |
| | LIST THE FLORIDA PRODUCT APPROVAL NEXT TO EACH |
| | SPECIFIED CONNECTOR. |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS (DOORS, |
| | WINDOWS AND ROOFING) AS REQUIRED BY SEC. 107.3.4.1 CITY |
| | AMENDMENTS. |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | 8- FLAT ROOF NOA 14-1030.02 SUBMITTED: |
| | A) CLEARLY MARK SPECIFIC APPROVED ASSEMBLY TO BE |
| | INSTALLED TO VERIFY COMPLIANCE WIT THE DESIGN PRESSURES |
| | OF SEC. R301.1 FBC-RESIDENTIAL. |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS (2 |
| | COPIES) AS REQUIRED BY GENERAL LIMITATION # 7 ON LAST |
| | PAGE OF NOA SUBMITTED. REQUIRED TO MEET THE DESIGN |
| | PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | 9- ROOF FRAMING PLAN: SPECIFY HOW ARE THE ROOF JOISTS |
| | CONNECTED TO THE "EXISTING CONCRETE BEAM". SEC. R301.1 |
| | FBC-RESIDENTIAL. NOTE: ACCORDING TO PLANS SUBMITTED ON |
| | EXPIRED PERMIT #14100767 THE EXISTING ROOM IS WOOD |
| | FRAME CONSTRUCTION NOT CONCRETE BLOCK. NOTE: COORDINATE |
| | WITH THE INTRODUCTORY NOTE ON THE TOP OF THIS SHEET AND |
| | ITEM # 3 ABOVE. |
| | |
| | 10- REVISE INFILL DETAIL ON SHEET A-1. NOTE: ACCORDING |
| | TO PLANS SUBMITTED ON EXPIRED PERMIT #14100767 THE |
| | EXISTING ROOM IS WOOD FRAME CONSTRUCTION NOT CONCRETE |
| | BLOCK. NOTE: COORDINATE WITH THE INTRODUCTORY NOTE ON |
| | THE TOP OF THIS SHEET AND ITEM # 3 ABOVE. SEC. 107.2.1 |
| | CITY AMENDMENTS. |
| | |
| | 11- THE SCOPE OF WORK IS NOT ALTERATION LEVEL 2. REVISE |
| | INFORMATION AT THE BOTTOM RIGHT OF SHEET A-1. SEE |
| | CHAPTER 5 OF FBC-EXISTING BUILDING, 5TH EDITION (2014) |
| | AND REFERENCE THE CORRECT CLASSIFICATION OF WORK FOR |
| | THE PROPOSED WORK AS REQUIRED BY SEC. 501.1 |
| | FBC-EXISTING BUILDING. |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |