Plan Review Notes
Plan Review Notes For Permit 16081110
Permit Number 16081110
Review Stop B
Sequence Number 2
Notes
Date Text
2017-02-14 17:52:33 
 05/24/17 MET W/ CONTRACTOR (JUNIOR) TO GO OVER
 COMMENTS. EXISTING ADDITION IN QUESTION WAS CLARIFIED.
 IT WAS BUILT LONG TIME AGO AND SHOWN ON THE GREEN CARD.
 JG.
  
  
 RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 THERE IS A CONFLICT WITH PERMIT #14100767 AND PLANS
 SUBMITTED NOW FOR THE BEDROOM ADDITION. PERMIT
 #14100767 WAS FOR AN STORAGE ROOM. PLANS SUBMITTED NOW
 INDICATE THAT THIS AREA IS LIVABLE AREA (NO STORAGE).
 IN 2014 PERMIT APPLICATION AND PLANS WERE SUBMITTED TO
 RE-OPEN EXPIRED PERMIT #99120889. PERMIT #14100767 WAS
 NEVER ISSUED. IT WAS ABANDONED. NEED TO INVESTIGATE IF
 THE WORK WAS DONE. THERE ARE NO PERMITS OR INSPECTIONS
 FOR THE WORK IN THIS AREA. FEES FOR WORK WITHOUT PERMIT
 MAY APPLY.
  
  
 1- BASED ON THE PRESCRIPTIVE ENERGY CALCULATIONS FORM
 R402-2014 SUBMITTED THE FOLLOWING ITEMS ARE REQUIRED:
 A) CONCRETE BLOCK WALL TO HAVE INSULATION ON THE
 INTERIOR AND EXTERIOR SIDE OF THE WALL. SEE TABLE R402A
 OF FORM R402-2014 SUBMITTED. ENGINEER OF RECORD TO
 PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING HOW
 THE INSULATION IS GOING TO BE INSTALLED ON BOTH SIDES
 OF THE WALL. SEC. R103.2 FBC-ENERGY CONSERVATION.
  
 B) NEED R-30 CEILING INSULATION. SEE TABLE R402A FOR
 MANDATORY REQUIREMENTS. R-30 BATT INSULATION DOESN'T
 FIT ON 2X8 ROOF JOISTS. R-30 BATT INSULATION IS ABOUT
 9-1/2" THICK. ALSO, NEED AT LEAST 1" CLEARANCE BETWEEN
 THE INSULATION AND THE ROOF SHEATHING FOR ROOF
 VENTILATION AS REQUIRED BY SEC. R806.3 FBC-RESIDENTIAL.
 REVISE PLANS AS REQUIRED.
  
  
 2- ENERGY CALCULATIONS PRESCRIPTIVE FORM R402-2014
 SUBMITTED: (NOTE: IF ITEMS REQUIRED BY TABLE R402A CAN
 NOT BE INSTALLED, THEN THIS PRESCRIPTIVE METHOD CAN NOT
 BE USED).
 A) CALCULATIONS NEED TO BE CERTIFIED AND DATED BY THE
 OWNER AT THE BOTTOM OF FORM AS REQUIRED BY SEC.
 R103.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 B) PROVIDE THE NAME OF THE PERSON WHO PREPARED THE
 ENERGY CALCULATIONS AND DATE IT WAS SIGNED AS REQUIRED
 BY SEC. 107.2.1 CITY AMENDMENTS.
  
 C) COMPLETE WINDOWS ITEM # 6(A) AND #6(B) AS REQUIRED
 BY SEC. R101.5.1.1.1 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014). NOTE: SEE TABLE R402A FOR MANDATORY
 REQUIREMENTS.
  
 D) COMPLETE FLOOR ITEM #8 AS REQUIRED BY SEC.
 R101.5.1.1.1 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014). NOTE: SEE TABLE R402A FOR MANDATORY
 REQUIREMENTS.
  
 E) COMPLETE WALL ITEM #9 AS REQUIRED BY SEC.
 R101.5.1.1.1 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014). NOTE: NEED INSULATION ON THE INTERIOR SIDE AND
 EXTERIOR SIDE OF THE CONCRETE BLOCK WALL. SEE TABLE
 R402A FOR MANDATORY REQUIREMENTS.
  
 F) COORDINATE CEILING R-VALUE ON ITEM #10 WITH REVISED
 INFORMATION REQUIRED BY ITEM #1(B) ABOVE. NOTE: IF R-30
 INSULATION CAN NOT BE INSTALLED, THEN THE PRESCRIPTIVE
 ENERGY CALCULATIONS FORM R402-2014 CAN NOT BE USED.
 SEC. R101.5.1.1.1 FBC-ENERGY CONSERVATION.
  
 G) COMPLETE ALL THE INFORMATION ON COOLING SYSTEM ITEM
 #12 (A) AND (B) AS REQUIRED BY SEC. R101.5.1.1.1
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 H) COMPLETE ALL THE INFORMATION ON HEATING SYSTEM ITEM
 #13 (A) AND (B) AS REQUIRED BY SEC. R101.5.1.1.1
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 I) COMPLETE ALL THE INFORMATION HVAC SIZING
 CALCULATIONS ON ITEM # 14 AS REQUIRED BY SEC.
 R101.5.1.1.1 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 J) COMPLETE ALL THE INFORMATION ON WATER HEATING SYSTEM
 ITEM #15 AS REQUIRED BY SEC. R101.5.1.1.1 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 K) COMPLETE ALL THE INFORMATION ON TABLES R402A AND
 TABLE R402B AS REQUIRED BY SEC. R101.5.1.1.1 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 L) BASED ON PLANS SUBMITTED, IT LOOKS LIKE THERE IS A
 LIVABLE AREA ADJACENT TO THE PROPOSED ADDITION. THIS
 AREA WAS NOT PERMITTED AND INSPECTED. COORDINATE WITH
 INTRODUCTORY NOTE ON TOP OF THIS SHEET AND ITEM #3
 BELOW. ENERGY CALCULATIONS NEED TO BE REVISED TO
 INCLUDE THE ADJACENT ROOM. SEC. R101.5.1.1.1 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 NOTE:
 LABEL FOR DOORS AND WINDOWS SHOWING THE U-FACTOR AND
 SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS WILL
 BE REQUIRED FOR INSPECTION.
  
  
 3- THE WEST WALL IS BLOCKED TO ALLOW FOR THE PROPOSED
 ADDITION. CLEARLY IDENTIFY ON PLANS THE ROOM (OR ROOMS)
 THAT ARE ADJACENT TO THE PROPOSED ADDITION. IF THERE IS
 ANY BEDROOM LOCATED ADJACENT TO THE PROPOSED ADDITION,
 THEN COMPLIANCE WITH THE EGRESS REQUIREMENTS NEED TO BE
 PROVIDED. SEC. R310 FBC-RESIDENTIAL, 5TH EDITION
 (2014).
 RESPONSE: AREA ADJACENT TO THE PROPOSED ADDITION IS
 SUPPOSED TO BE STORAGE NOT LIVABLE AREA. (SEE
 INTRODUCTORY NOTE ON TOP OF THIS SHEET REGARDING
 CONFLICT WITH ABANDONED PERMITS). NEED TO PROVIDE
 COMPLETE PLANS/DETAILS/ SPECIFICATIONS AND PRODUCT
 APPROVALS FOR THE AREA ADJACENT TO THE PROPOSED
 ADDITION. ADDITIONAL COMMENTS MAY ARISE BASED ON THE
 INFORMATION SUBMITTED AND VALUATION NEED TO BE UPDATED
 AS WELL TO INCLUDE THE ADDITONAL SCOPE OF WORK.
  
 4- REVISE ROOF SLOPE SHOWN ON THE EXTERIOR ELEVATIONS.
 THE REQUIRED SLOPE IS 1/4" PER FT MIN. SEC. R905.9
 FBC-RESIDENTIAL.
 RESPONSE: REPEAT COMMENT.
  
 5- TYPICAL WALL SECTION ON SHEET A-1:
 A) NEED TO PROVIDE ROOF CROSS VENTILATION AS REQUIRED
 BY SEC. R806 FBC-RESIDENTIAL. SPECIFIED VENTS DON'T
 PROVIDE CROSS VENTILATION ON THE TYPE OF PROPOSED ROOF
 (FLAT). NOTE: THE 2"X8" BRACING SHOWN ON THE ROOF
 FRAMING PLAN IS ALSO BLOCKING THE CROSS VENTILATION.
 NEED TO PROVIDE AT LEAST 1" VENT AND INSULATION
 CLEARANCE AS REQUIRED BY SEC. R806.3 FBC-RESIDENTIAL.
 RESPONSE: REPEAT COMMENT. SPECIFIED VENTS DON'T PROVIDE
 CROSS VENTILATION. THEY ONLY PROVIDE VENTILATION WHERE
 THE VENT IS LOCATED. THIS TYPE OF ROOF NEEDS CONTINUOUS
 VENT. ALSO, R-30 BATT INSULATION IS 9-1/2" THICK. IT
 DOESN'T FIT ON 2 X 8 ROOF JOISTS. IN ADDITION R-30
 INSULATION DOESN'T ALLOW FOR THE 1" VENT INSULATION
 CLEARANCE. REVISE AS REQUIRED. COORDINATE WITH THE
 REQUIRED REVISED ENERGY CALCULATIONS AND ITEM #1(B)
 ABOVE.
  
 B) SPECIFY THE WALL INSULATION. NOTE: COORDINATE WITH
 THE ENERGY CALCULATIONS AND COMMENT # 1(A) ABOVE. SEC.
 R103.2 FBC-ENERGY CONSERVATION.
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) SINGLE HUNG WINDOWS AS SHOWN ON PLANS. DWGS NO
 08-02476 SUBMITTED DON'T HAVE A FLORIDA PRODUCT
 APPROVAL NUMBER OR MIAMI-DADE NOA NUMBER. PROVIDE
 FLORIDA OR MIAMI-DADE COVER PAGE THAT CORRESPONDS TO
 DRAWINGS SUBMITTED. IF THERE IS NOT CURRENT FLORIDA OR
 MIAMI-DADE APPROVAL, THEN MANUFACTURER MAY APPLY FOR
 LOCAL PRODUCT APPROVAL BY SUBMITTING COMPLETE ORIGINAL
 ENGINEER PACKAGE FOR BUILDING OFFICIAL APPROVAL. ADVICE
 IF APPLYING FOR LOCAL PRODUCT APPROVAL FOR FURTHER
 INSTRUCTIONS.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED. PROVIDE
 FLORIDA PRODUCT APPROVAL COVER PAGE THAT CORRESPOND TO
 DRAWINGS SUBMITTED.
  
 B) PRECAST LINTELS AS SPECIFIED ON PLANS.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 C) SIMPSON STRUCTURAL CONNECTORS AS SPECIFIED ON PLANS.
 PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL COVER PAGE
 AND PAGE SHOWING THE SPECIFIED CONNECTOR OR ENGINEER TO
 LIST THE FLORIDA PRODUCT APPROVAL NEXT TO EACH
 SPECIFIED CONNECTOR.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS (DOORS,
 WINDOWS AND ROOFING) AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 8- FLAT ROOF NOA 14-1030.02 SUBMITTED:
 A) CLEARLY MARK SPECIFIC APPROVED ASSEMBLY TO BE
 INSTALLED TO VERIFY COMPLIANCE WIT THE DESIGN PRESSURES
 OF SEC. R301.1 FBC-RESIDENTIAL.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS (2
 COPIES) AS REQUIRED BY GENERAL LIMITATION # 7 ON LAST
 PAGE OF NOA SUBMITTED. REQUIRED TO MEET THE DESIGN
 PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 9- ROOF FRAMING PLAN: SPECIFY HOW ARE THE ROOF JOISTS
 CONNECTED TO THE "EXISTING CONCRETE BEAM". SEC. R301.1
 FBC-RESIDENTIAL. NOTE: ACCORDING TO PLANS SUBMITTED ON
 EXPIRED PERMIT #14100767 THE EXISTING ROOM IS WOOD
 FRAME CONSTRUCTION NOT CONCRETE BLOCK. NOTE: COORDINATE
 WITH THE INTRODUCTORY NOTE ON THE TOP OF THIS SHEET AND
 ITEM # 3 ABOVE.
  
 10- REVISE INFILL DETAIL ON SHEET A-1. NOTE: ACCORDING
 TO PLANS SUBMITTED ON EXPIRED PERMIT #14100767 THE
 EXISTING ROOM IS WOOD FRAME CONSTRUCTION NOT CONCRETE
 BLOCK. NOTE: COORDINATE WITH THE INTRODUCTORY NOTE ON
 THE TOP OF THIS SHEET AND ITEM # 3 ABOVE. SEC. 107.2.1
 CITY AMENDMENTS.
  
 11- THE SCOPE OF WORK IS NOT ALTERATION LEVEL 2. REVISE
 INFORMATION AT THE BOTTOM RIGHT OF SHEET A-1. SEE
 CHAPTER 5 OF FBC-EXISTING BUILDING, 5TH EDITION (2014)
 AND REFERENCE THE CORRECT CLASSIFICATION OF WORK FOR
 THE PROPOSED WORK AS REQUIRED BY SEC. 501.1
 FBC-EXISTING BUILDING.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]