| 2016-09-13 11:00:33 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | JOB ADDRESS: 7604 MARTIN AVE. |
| | DESCRIPTION: BUILD-OUT AS PER PLANS |
| | MASTER PERMIT: 16081110 |
| | |
| | BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS. |
| | ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF |
| | SUBMITTED CORRECTIONS. |
| | |
| | 1. YOU SHALL SUBMIT A SITE PLAN SHOWING THE LOCATION OF |
| | THE ELECTRIC METER AND ASSOCIATED APPARATUS AND THE |
| | ELECTRIC UTILITY SERVICE POLE. INDICATE ON IT IF THE |
| | SERVICE IS UNDERGROUND OR OVERHEAD. FURTHERMORE YOU |
| | SHALL SHOW THE LOCATION OF THE EXISTING PANEL. INDICATE |
| | IF THERE IS A DISCONNECT ON THE EXTERIOR OF THE |
| | RESIDENCE. |
| | 2. YOU SHALL SUBMIT A SITE SPECIFIC ELECTRICAL RISER |
| | DIAGRAM MATCHING THE ABOVE MENTIONED. |
| | 3. NOTE THAT IT IS THE AMBIENT CONDITIONS WHICH |
| | DETERMINE CONDUCTOR INSULATION TYPE AND NOT THE WIRE |
| | GAUGE. ALL CONDUCTORS EXPOSED TO DAMP OR WET LOCATIONS |
| | SHALL BE LISTED ACCORDINGLY REGARDLESS OF GAUGE. |
| | CORRECT NOTE 8 OF THE ELECTRICAL NOTES. |
| | 4. FBC-R3706.2 NEC 408.4(A) REQUIRES THAT YOU PROVIDE A |
| | PANEL SCHEDULE OR CIRCUIT DIRECTORY LEGIBLY INDICATING |
| | THE SPECIFIC PURPOSE OF EVERY CIRCUIT. THIS APPLIES TO |
| | ALL PANELS OF THE HOME. INDICATE WHETHER MAIN BREAKER |
| | OR MAIN LUG ONLY. |
| | 5. FBC-ER3901.12 NEC 210.63 HVAC EQUIPMENT SERVICE |
| | OUTLET. A 125 VOLT, SINGLE-PHASE, 15 OR 20-AMPERE-RATED |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE |
| | LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE |
| | RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE |
| | EQUIPMENT AND THE DEVICE LISTED WEATHER-RESISTANT AS |
| | INDICATED BY FBC-R4002.9. |
| | 6. FBC-RE3901.2.1 NEC 210.52 (A)(1) SPACING. |
| | RECEPTACLES SHALL BE INSTALLED SUCH THAT NO POINT |
| | MEASURED HORIZONTALLY ALONG THE FLOOR LINE IN ANY WALL |
| | SPACE IS MORE THAN 6 FT. FROM A RECEPTACLE OUTLET. THIS |
| | INCLUDES THE DISTANCE FROM THE EDGE OF THE WALL. |
| | 7. FBC-RE3901.2.2 NEC 210.52 (A)(2) WALL SPACE. ANY |
| | WALL SPACE 2 FT. OR MORE IN WIDTH SHALL REQUIRE A |
| | RECEPTACLE. THIS APPLIES TO WALL SPACE BETWEEN BATHROOM |
| | AND CLOSET. |
| | 8. FBC-RE3905.8 NEC 314.27(D) PADDLE FANS. BOXES USED |
| | FOR THE SOLE SUPPORT OF CEILING FANS SHALL BE MARKED BY |
| | THE MANUFACTURER AS SUITABLE FOR THE PURPOSE, AND |
| | INDICATE THE WEIGHT LIMITATIONS BUT SHALL NOT BE USED |
| | TO SUPPORT PADDLE FANS HEAVIER THAN 70 LBS. THIS CAN BE |
| | ADDRESSED WITH A BLOCK NOTE. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |