2016-09-13 11:00:33ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 JOB ADDRESS: 7604 MARTIN AVE.
 DESCRIPTION: BUILD-OUT AS PER PLANS
 MASTER PERMIT: 16081110
  
 BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS.
 ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF
 SUBMITTED CORRECTIONS.
  
 1. YOU SHALL SUBMIT A SITE PLAN SHOWING THE LOCATION OF
 THE ELECTRIC METER AND ASSOCIATED APPARATUS AND THE
 ELECTRIC UTILITY SERVICE POLE. INDICATE ON IT IF THE
 SERVICE IS UNDERGROUND OR OVERHEAD. FURTHERMORE YOU
 SHALL SHOW THE LOCATION OF THE EXISTING PANEL. INDICATE
 IF THERE IS A DISCONNECT ON THE EXTERIOR OF THE
 RESIDENCE.
 2. YOU SHALL SUBMIT A SITE SPECIFIC ELECTRICAL RISER
 DIAGRAM MATCHING THE ABOVE MENTIONED.
 3. NOTE THAT IT IS THE AMBIENT CONDITIONS WHICH
 DETERMINE CONDUCTOR INSULATION TYPE AND NOT THE WIRE
 GAUGE. ALL CONDUCTORS EXPOSED TO DAMP OR WET LOCATIONS
 SHALL BE LISTED ACCORDINGLY REGARDLESS OF GAUGE.
 CORRECT NOTE 8 OF THE ELECTRICAL NOTES.
 4. FBC-R3706.2 NEC 408.4(A) REQUIRES THAT YOU PROVIDE A
 PANEL SCHEDULE OR CIRCUIT DIRECTORY LEGIBLY INDICATING
 THE SPECIFIC PURPOSE OF EVERY CIRCUIT. THIS APPLIES TO
 ALL PANELS OF THE HOME. INDICATE WHETHER MAIN BREAKER
 OR MAIN LUG ONLY.
 5. FBC-ER3901.12 NEC 210.63 HVAC EQUIPMENT SERVICE
 OUTLET. A 125 VOLT, SINGLE-PHASE, 15 OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE
 EQUIPMENT AND THE DEVICE LISTED WEATHER-RESISTANT AS
 INDICATED BY FBC-R4002.9.
 6. FBC-RE3901.2.1 NEC 210.52 (A)(1) SPACING.
 RECEPTACLES SHALL BE INSTALLED SUCH THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE IN ANY WALL
 SPACE IS MORE THAN 6 FT. FROM A RECEPTACLE OUTLET. THIS
 INCLUDES THE DISTANCE FROM THE EDGE OF THE WALL.
 7. FBC-RE3901.2.2 NEC 210.52 (A)(2) WALL SPACE. ANY
 WALL SPACE 2 FT. OR MORE IN WIDTH SHALL REQUIRE A
 RECEPTACLE. THIS APPLIES TO WALL SPACE BETWEEN BATHROOM
 AND CLOSET.
 8. FBC-RE3905.8 NEC 314.27(D) PADDLE FANS. BOXES USED
 FOR THE SOLE SUPPORT OF CEILING FANS SHALL BE MARKED BY
 THE MANUFACTURER AS SUITABLE FOR THE PURPOSE, AND
 INDICATE THE WEIGHT LIMITATIONS BUT SHALL NOT BE USED
 TO SUPPORT PADDLE FANS HEAVIER THAN 70 LBS. THIS CAN BE
 ADDRESSED WITH A BLOCK NOTE.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER