| 2016-10-13 10:01:53 | 2ND ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | JOB ADDRESS: 1308 LAKE AVE A |
| | DESCRIPTION: BATHROOM & KITCHEN RENOVATION |
| | MASTER PERMIT: 16081099 |
| | |
| | BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS. |
| | ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF |
| | SUBMITTED CORRECTIONS. |
| | |
| | 1. PER FBC MECHANICAL VENTILATION IS REQUIRED IN THE |
| | TOILET ROOM WHENEVER THE ROOM IS OCCUPIED. THEREFORE |
| | THE EXHAUST FAN SHALL BE CONTROLLED WITH THE LIGHT TO |
| | COME ON SIMULTANEOUSLY. |
| | 2. FBC-RE3901.6 BATHROOMS. IN DWELLING UNITS, AT LEAST |
| | ONE RECEPTACLE OUTLET SHALL BE INSTALLED IN BATHROOMS |
| | WITHIN 3 FT. OF THE OUTSIDE EDGE OF EACH BASIN. YOU |
| | ONLY HAVE ONE ADJACENT TO ONE OF THE BASINS. AS SECOND |
| | OUTLET IS REQUIRED OR THIS ONE SHALL BE RELOCATED |
| | ACCORDINGLY. |
| | 3. FBC-RE3901.2.2 WALL SPACE. ANY WALL SPACE 2 FT. OR |
| | MORE IN WIDTH SHALL REQUIRE A RECEPTACLE. IF THE |
| | DEDICATED DISHWASHER OUTLET IS HIDDEN UNDERNEATH THE |
| | COUNTER, AND THE SPACE BETWEEN THE RANGE AND SINK IS |
| | GREATER THAN 4 FT., AN ADDITIONAL OUTLET IS REQUIRED |
| | FOR THE AREA |
| | 4. THE SMOKE DETECTOR IN THE KITCHEN AREA IS NOT |
| | REQUIRED. IF YOU ARE TO HAVE ONE IN THE KITCHEN, IT |
| | SHALL BE OF THE PHOTOELECTRIC TYPE AND BE GREATER THAN |
| | 6 FT. FROM THE COOKING APPLIANCE. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |