2016-08-31 11:22:14ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 &
 NFPA 70 2011 (NEC)
  
 PROJECT NAME:
 JOB ADDRESS: 1308 LAKE AVE A
 DESCRIPTION: KITCHEN & BATH REMODEL
 MASTER PERMIT: 16081099
  
 WITH THE EXCEPTION OF ITEM #1 BELOW, EVERYTHING ELSE
 CAN BE ADDRESSED WITH A BLOCK NOTE ON THE PLANS. NO
 NEED TO COPY VERBATIM BUT ADDRESS THE INTENT.
  
 1. YOU SHALL PROVIDE AN ELECTRICAL SHEET SHOWING THE
 LOCATION OF ALL ELECTRICAL DEVICES WITHIN THE AREA OF
 WORK. YOU ARE TO INDICATE ON THE SHEET IF THESE DEVICES
 ARE EITHER EXISTING TO REMAIN OR NEW. THE FINISHED
 PRODUCT SHALL HAVE RECEPTACLES SPACED ACCORDING TO 2011
 NEC. KEEP IN MIND THE RECEPTACLE PLACEMENT REQUIREMENTS
 FOR THE BATHROOM BASIN ONCE CONVERTED TO A DOUBLE SINK
 SET UP. THE SAME HOLD TRUE FOR THE KITCHEN.
 2. SECTION 107.2.1 OF THE WPB CITY AMENDMENTS REQUIRE
 THAT THE CONSTRUCTION DOCUMENTS BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE PROPOSED WORK AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO CODE REQUIREMENTS. (CLEARLY DEFINE YOUR
 SCOPE OF WORK ON THE PLANS). SUCH DRAWINGS SHALL
 INDICATE THE APPLICABLE DESIGN CODE, AND FURTHERMORE,
 THE DRAWINGS SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. (YOUR NAME AND
 SIGNATURE SHALL APPEAR ON ALL DOCUMENTS).
 3. FBC-B109.3 BUILDING PERMIT VALUATIONS: IN MY OPINION
 THE DECLARED VALUE OF THIS PERMIT IS UNDER ESTIMATED
 AND THEREFORE YOU SHALL PROVIDE A SIGNED COPY OF THE
 ACCEPTED CONTRACT TO PROVE THE DECLARED VALUE STATED ON
 PERMIT.
 4. FBC-R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS: IF
 NOT ALREADY IN COMPLIANCE WITH SMOKED DETECTOR
 REQUIREMENTS FOR FINAL INSPECTION YOU SHALL INSTALL
 SMOKE DETECTORS AS IF THIS WERE A NEW HOME.
 5. FBC-R315.1 CARBON MONOXIDE PROTECTION: IF THERE IS
 AN ATTACHED GARAGE OF ANY FOSSIL FUEL (GAS) BURNING
 APPLIANCES IN THE RESIDENCE YOU SHALL INSTALL CARBON
 MONOXIDE DETECTORS PER CODE.
 6. FBC-R4002.14/NEC 406.12 TAMPER-RESISTANT RECEPTACLES
 IN DWELLING UNITS: ALL OF THE RECEPTACLES IN THE
 REMODELED AREA SHALL BE TAMPER RESISTANT.
 7. FBC-RE3902.11/NEC 210.8 GROUND FAULT
 CIRCUIT-INTERRUPTER PROTECTION: ALL OUTLETS SERVING THE
 KITCHEN COUNTER AND WITHIN 6? OF THE BATHROOM SINK
 SHALL BE GFCI PROTECTED.
 8. FBC-RE3906.5/NEC 314.20 IN WALL OR CEILING: MAKE
 CERTAIN THAT ALL OUTLET BOXES INSTALLED IN NEW WALLS
 ARE NO MORE THAN ?? FROM THE WALL SURFACE.
 9. FBC-RE3906.6/NEC 314.21 REPAIRING NONCOMBUSTIBLE
 SURFACES: MAKE CERTAIN THAT ALL OUTLET BOXES IN THE
 KITCHEN BACK SPLASH ARE NO MORE THAN 1/8? FROM THE
 EDGE.
 10. FBC-ER404.1 A MINIMUM OF 75% OF THE LAMPS IN
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE
 HIGH-EFFICACY LAMPS OR A MINIMUM OF 75% OF THE
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN
 ONLY HIGH EFFICIENCY LAMPS
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  