| 2016-08-31 11:22:14 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 & |
| | NFPA 70 2011 (NEC) |
| | |
| | PROJECT NAME: |
| | JOB ADDRESS: 1308 LAKE AVE A |
| | DESCRIPTION: KITCHEN & BATH REMODEL |
| | MASTER PERMIT: 16081099 |
| | |
| | WITH THE EXCEPTION OF ITEM #1 BELOW, EVERYTHING ELSE |
| | CAN BE ADDRESSED WITH A BLOCK NOTE ON THE PLANS. NO |
| | NEED TO COPY VERBATIM BUT ADDRESS THE INTENT. |
| | |
| | 1. YOU SHALL PROVIDE AN ELECTRICAL SHEET SHOWING THE |
| | LOCATION OF ALL ELECTRICAL DEVICES WITHIN THE AREA OF |
| | WORK. YOU ARE TO INDICATE ON THE SHEET IF THESE DEVICES |
| | ARE EITHER EXISTING TO REMAIN OR NEW. THE FINISHED |
| | PRODUCT SHALL HAVE RECEPTACLES SPACED ACCORDING TO 2011 |
| | NEC. KEEP IN MIND THE RECEPTACLE PLACEMENT REQUIREMENTS |
| | FOR THE BATHROOM BASIN ONCE CONVERTED TO A DOUBLE SINK |
| | SET UP. THE SAME HOLD TRUE FOR THE KITCHEN. |
| | 2. SECTION 107.2.1 OF THE WPB CITY AMENDMENTS REQUIRE |
| | THAT THE CONSTRUCTION DOCUMENTS BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE PROPOSED WORK AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO CODE REQUIREMENTS. (CLEARLY DEFINE YOUR |
| | SCOPE OF WORK ON THE PLANS). SUCH DRAWINGS SHALL |
| | INDICATE THE APPLICABLE DESIGN CODE, AND FURTHERMORE, |
| | THE DRAWINGS SHALL BEAR THE NAME AND SIGNATURE OF THE |
| | PERSON RESPONSIBLE FOR THE DESIGN. (YOUR NAME AND |
| | SIGNATURE SHALL APPEAR ON ALL DOCUMENTS). |
| | 3. FBC-B109.3 BUILDING PERMIT VALUATIONS: IN MY OPINION |
| | THE DECLARED VALUE OF THIS PERMIT IS UNDER ESTIMATED |
| | AND THEREFORE YOU SHALL PROVIDE A SIGNED COPY OF THE |
| | ACCEPTED CONTRACT TO PROVE THE DECLARED VALUE STATED ON |
| | PERMIT. |
| | 4. FBC-R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS: IF |
| | NOT ALREADY IN COMPLIANCE WITH SMOKED DETECTOR |
| | REQUIREMENTS FOR FINAL INSPECTION YOU SHALL INSTALL |
| | SMOKE DETECTORS AS IF THIS WERE A NEW HOME. |
| | 5. FBC-R315.1 CARBON MONOXIDE PROTECTION: IF THERE IS |
| | AN ATTACHED GARAGE OF ANY FOSSIL FUEL (GAS) BURNING |
| | APPLIANCES IN THE RESIDENCE YOU SHALL INSTALL CARBON |
| | MONOXIDE DETECTORS PER CODE. |
| | 6. FBC-R4002.14/NEC 406.12 TAMPER-RESISTANT RECEPTACLES |
| | IN DWELLING UNITS: ALL OF THE RECEPTACLES IN THE |
| | REMODELED AREA SHALL BE TAMPER RESISTANT. |
| | 7. FBC-RE3902.11/NEC 210.8 GROUND FAULT |
| | CIRCUIT-INTERRUPTER PROTECTION: ALL OUTLETS SERVING THE |
| | KITCHEN COUNTER AND WITHIN 6? OF THE BATHROOM SINK |
| | SHALL BE GFCI PROTECTED. |
| | 8. FBC-RE3906.5/NEC 314.20 IN WALL OR CEILING: MAKE |
| | CERTAIN THAT ALL OUTLET BOXES INSTALLED IN NEW WALLS |
| | ARE NO MORE THAN ?? FROM THE WALL SURFACE. |
| | 9. FBC-RE3906.6/NEC 314.21 REPAIRING NONCOMBUSTIBLE |
| | SURFACES: MAKE CERTAIN THAT ALL OUTLET BOXES IN THE |
| | KITCHEN BACK SPLASH ARE NO MORE THAN 1/8? FROM THE |
| | EDGE. |
| | 10. FBC-ER404.1 A MINIMUM OF 75% OF THE LAMPS IN |
| | PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE |
| | HIGH-EFFICACY LAMPS OR A MINIMUM OF 75% OF THE |
| | PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN |
| | ONLY HIGH EFFICIENCY LAMPS |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |