| 2016-10-18 10:55:12 | 2ND ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 | | | PREVIOUS PROVISO COMMENTS: | | | | | | 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE | | | PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE | | | PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL LOW | | | VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE | | | ALARM, PHONE AND DATA, ELECTRICAL RELATED TO HOOD | | | SYSTEM SHOWN ETC. A NOTE WILL SUFFICE. | | | 2. PLEASE SHOW THAT THE EXISTING ROOFTOP RECEPTACLES | | | ARE W/P GFCI PROTECTED. | | | 3. SHEET E301- PROVIDE A GENERAL NOTE TO INDICATE NEC | | | 210.8B2 GFCI AT FOOD PREP AREA AND KITCHENS. A NOTE | | | WILL SUFFICE | | | | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | |
|