| 2016-09-10 10:27:36 | 1) SHT. CS-2 REFERS TO THE 2010 FBC. THE CODE IN EFFECT |
| | IS THE 2014 FBC. PLEASE REVISE THE CODE REFERENCES. |
| | 2) SHT. P201 REFERENCES THE 2010 AND THE 2014 GAS CODE. |
| | THE CODE IN EFFECT IS THE 2014 FUEL GAS CODE. REVISE |
| | THE NOTES. |
| | 3) P201- THE 2 PSI GAS TABLE THAT IS REFERENCED IS FOR |
| | PRESSURE LESS THAN 2 PSI IN THE 2014 FGC. REVISE THE |
| | STANDARD AND GAS TABLE. |
| | 4) SHT. P201 SHOWS A LOW PRESSURE ONE INCH GAS LINE |
| | SUPPLYING 452 MBTU'S AND ALSO A 1 1/4 INCH GAS LINE |
| | SUPPLYING THE 452 MBTU'S. CLARIFY. THE MINIMUM SIZE |
| | SHALL BE 1 1/4 INCHES. THIS IS ALSO SHOWN ON THE |
| | PARTIAL PLAN. |
| | 5) SHOW THE REQUIRED SHUTOFF VALVE UPSTREAM OF THE |
| | MEDIUM PRESSURE REGULATOR PER THE 2014 FGC SEC. 409.4. |
| | 6) SIZE THE GAS BRANCHES TO ALL THE APPLIANCES. COMPLY |
| | WITH 2014 FGC. |
| | 7) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS |
| | APPLIANCES. IF COMBUSTION AIR IS MECHANICALLY SUPPLIED |
| | THROUGH AN HVAC SYSTEM, THE SYSTEM MUST DELIVER THE |
| | REQUIRED COMBUSTION AIR RATE ABOVE AND BEYOND ANY |
| | OUTDDOOR AIR RATE SUPPLIED FOR VENTILATION OF THE |
| | OCCUPIED SPACES. FGC SEC.304.9.3.8) |
| | 8) SHT. P101 - IS THE ICE FLAKER BEING DISCHARGED INTO |
| | THE GREASY WASTE? WASTES THAT DO NOT REQUIRE TREATMENT |
| | OR SEPARATION SHALL NOT BE DISCHARGED INTO ANY |
| | INTERCEPTOR OR SEPARATOR. FPC SEC.1003.2. |
| | 9) SHT. REM 2.1 - INDICATE IF THE WATER HEATERS IN THE |
| | MEZZANINE AREA ARE NEW OR EXISTING TO REMAIN. |
| | |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |