| 2016-08-29 17:10:04 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | PROJECT NAME: 1250 ELIZABETH AVENUE |
| | JOB ADDRESS: 1250 ELIZABETH AVENUE |
| | DESCRIPTION: SQUASH COURTS, WAREHOUSE, |
| | OFFICE-RENOVATING EXISTING SPACE |
| | MASTER PERMIT: 16081096 |
| | |
| | BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS. |
| | ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF |
| | SUBMITTED CORRECTIONS. |
| | |
| | 1. IN YOUR GENERAL ELECTRICAL NOTES ON SHEET E0.1, YOUR |
| | NOTE 2 SHALL QUOTE THE SPECIFIC APPLICABLE CODES AND |
| | NOT GENERALIZATION. NOTE 3 DICTATES CONDUCTOR |
| | INSULATION BASED ON SIZE. CONDUCTOR INSULATION IS |
| | DETERMINED BY THE APPLICATION AND NOT SIZE. A |
| | CONDUCTOR, NO MATTER WHAT SIZE IN A WET LOCATION SHALL |
| | BE INSULATED ACCORDINGLY. |
| | 2. NEC 230.2(E) REQUIRES THAT EACH SERVICE BE PLACARDED |
| | TO INDICATE THE EXISTENCE AND LOCATION OF ANY OTHER |
| | SERVICE SUPPLYING THE BUILDING. |
| | 3. NEC 600.5 STATES THAT EACH COMMERCIAL BUILDING AND |
| | EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO PEDESTRIANS |
| | SHALL BE PROVIDED WITH AT LEAST ONE 20 AMP DEDICATED |
| | OUTLET IN AN ACCESSIBLE LOCATION AT EACH ENTRANCE TO |
| | EACH TENANT SPACE FOR SIGN OR OUTLINE LIGHTING. SERVICE |
| | HALLWAYS OR CORRIDORS SHALL NOT BE CONSIDERED |
| | ACCESSIBLE TO PEDESTRIANS. I DO NOT SEE THIS ON ANY OF |
| | THE DOORS ON EITHER THE POWER OR LIGHTING PLAN. |
| | 4. NEC 210.62 CALLS FOR AT LEAST ONE RECEPTACLE OUTLET |
| | TO BE INSTALLED WITHIN 18? OF THE TOP OF A SHOW WINDOW |
| | FOR EVERY 12 LINEAR FT. OR MAJOR PORTION THEREOF AREA |
| | MEASURED HORIZONTALLY. THIS APPLIES TO THE STORE FRONT |
| | AREAS OF THIS BLDG. |
| | 5. NEC 406.9(B) RECEPTACLES IN WET LOCATIONS. 15 AND 20 |
| | AMPERE, 125 AND 250 VOLT RECEPTACLES INSTALLED IN A WET |
| | LOCATION SHALL HAVE AN ENCLOSURE THAT IS WEATHERPROOF |
| | WHETHER OR NOT THE ATTACHMENT PLUG CAP IS INSERTED. ALL |
| | 15 AND 20 AMPERE, 125 AND 250 VOLT NONLOCKING |
| | RECEPTACLES SHALL BE LISTED WEATHER-RESISTANT TYPE |
| | ?WR?. CORRECT DETAIL 3 ON SHEET E5.1 TO COMPLY. ( |
| | REQUIRES AN IN-USE TYPE COVER). |
| | 6. FBC-B 1006.3 REQUIRES THAT THE EXIT DISCHARGE BE |
| | ILLUMINATED UNDER EMERGENCY POWER. THE SUBMITTED |
| | DRAWINGS DO SHOW EXTERIOR LIGHTING BUT NOT ANY |
| | EMERGENCY LIGHTING. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |