2016-08-26 17:13:08PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PROJECT IS LOCATED WITHIN 600 FEET OF THE
 INTERCOASTAL WATERWAY AND IS THEREFORE AN EXPOSURE D.
 FBC R301.2.1.4.3
  
 2) SHOW COMPLIANCE WITH 708.8. WHEN A ROOF COVERING ON
 AN EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL
 STRUCTURE IS REMOVED AND REPLACED ON A BUILDING THAT IS
 LOCATED IN THE WIND-BORNE DEBRIS REGION AS DEFINED IN
 THE FLORIDA BUILDING CODE, BUILDING AND THAT HAS AN
 INSURED VALUE OF $300,000 OR MORE OR, IF THE BUILDING
 IS UNINSURED OR FOR WHICH DOCUMENTATION OF INSURED
 VALUE IS NOT PRESENTED, HAS A JUST VALUATION FOR THE
 STRUCTURE FOR PURPOSES OF AD VALOREM TAXATION OF
 $300,000 OR MORE:
 (A) ROOF TO WALL CONNECTIONS SHALL BE IMPROVED AS
 REQUIRED BY SECTION 708.8.1.
 (B) MANDATED RETROFITS OF THE ROOF-TO-WALL CONNECTION
 SHALL NOT BE REQUIRED BEYOND A 15-PERCENT INCREASE IN
 THE COST OF REROOFING.
  
  
  