Plan Review Notes
Plan Review Notes For Permit 16081063
Permit Number 16081063
Review Stop G
Sequence Number 1
Notes
Date Text
2016-08-27 02:54:34 
  
 1) THE GAS RISER HAS BEEN DONE IN AN ERASABLE FORMAT (
 PENCIL? ) AND IS UNACCEPTABLE. SUBMIT 2 COPIES OF THE
 GAS RISER IN AN ACCEPTABLE FORMAT. WPB AMEND. TO FBC
 SEC. 107..1, 107.2.1.
 2) THE LOCATION OF THE GAS METER AND SOME NOTES HAVE
 BEEN CUT OFF OF THE GAS RISER DRAWING. SUBMIT 2 COPIES
 OF THE GAS RISER DIAGRAM THAT CLEARLY SHOWS THE NOTES
 AND THE LOCATION OF THE METER.
 3) SHOW THE CORRESPONDING EHD NUMBER OF THE 1 INCH CSST
 SUPPLYING THE COOKTOP. COMPLY WITH 2014 FGC TABLES
 402.4 (15), 402.4 (16) OR 402.4 (17).
 4) THE GAS RISER SHOWS A DISTANCE OF 50 FEET(?) FROM
 THE METER TO THE 2ND STAGE REGULATOR BUT THE PLAN VIEW
 SHOWS 40 FEET. CLARIFY.
 5) SIZE THE BRANCH LINES TO THE POOL HEATER AND TO THE
 TANKLESS WATER HEATER . COMPLY WITH 2014 FGC SEC.402.3.
 6) SHOW THE LOCATION OF ANY WINDOWS OR DOORS ON THE
 PLAN VIEW DRAWING IN RELATION TO THE LOCATION OF THE
 TANKLESS WATER HEATER. SOFFIT VENTS SHALL ALSO BE TAKEN
 INTO CONSIDERATION. THE LOCATION OF THE TANKLESS WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS AND THE FGC SEC.503. SUBMIT
 TWO COPIES OF THE PAGES FROM THE MANUFACTURER'S
 INSTALLATION MANUAL THAT SHOWS THE HEATER LOCATION
 REQUIREMENTS. IF THERE IS A DIFFERENCE BETWEEN THE CODE
 AND THE INSTALLATION MANUAL, THE MOST RESTRICTIVE SHALL
 APPLY.WPB AMEND. TO FBC SEC.102.1.
 7) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE TANKLESS WATER HEATER AND THE
 COOKTOP. THE APPLIANCES SHALL BE LISTED AND LABELED PER
 THE FGC SEC. 301.3, WPB AMEND. TO FBC SEC. 107.2.1.
 8) SIZE THE SECTION OF GALVANIZED PIPE BETWEEN THE 2ND
 STAGE REGULATOR AND THE TANKLESS WATER HEATER.
 9) MANUF. SPECIFICATION SHEETS FOR THE REGULATORS SHALL
 BE ONSITE FOR INSPECTION.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  