| 2016-09-15 11:58:27 | RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1- CLEARLY SPECIFY SIZE AND TYPE OF EXISTING BEDROOM |
| | WINDOWS AND TYPE AND SIZE OF PROPOSED BEDROOM WINDOWS |
| | TO VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENTS OF |
| | SEC. 704 OF FBC-EXISTING BUILDING, 5TH EDITION (2014). |
| | |
| | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) ENTRY DOOR, UTILITY DOOR AND REAR DOUBLE DOORS. NEED |
| | PRODUCT APPROVAL THAT MEETS THE DESIGN PRESSURES AS |
| | REQUIRED BY SEC. R301.2.1.4 FBC-RESIDENTIAL, 5TH |
| | EDITION (2014). DOORS SUBMITTED WITH FLORIDA PRODUCT |
| | APPROVAL FL14569-R5 DON'T MEET THE DESIGN PRESSURES. |
| | NOTE: THIS BUILDING IS LOCATED IN EXPOSURE "D". NEED |
| | DOORS THAT MEET THE DESIGN PRESSURES FOR THIS EXPOSURE |
| | CATEGORY. |
| | |
| | 3- CLEARLY SPECIFY ON WINDOW MULLION PRODUCT APPROVAL |
| | SUBMITTED THE SIZE OF WINDOW MULLION TO BE INSTALLED TO |
| | VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. |
| | R301.2.1.4 FBC-RESIDENTIAL. |
| | |
| | 4- VALUATION DECLARED IN THE PERMIT APPLICATIONS SEEMS |
| | TO BE LOW BASED ON ALL THE SCOPE OF WORK SHOWN ON PLANS |
| | SUBMITTED. VALUATION TO INCLUDE ALL LABOR, MATERIALS |
| | AND CONTRACTORS' OVERHEAD AND PROFIT AS REQUIRED BY |
| | SEC. 109.3 CITY AMENDMENTS. UPDATE VALUATION AND |
| | PROVIDE COPY OF SIGNED CONTRACT FOR BUILDING OFFICIAL |
| | APPROVAL. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | (561)805-6712 |
| | [email protected] |
| | |
| | |