| 2016-11-02 17:48:35 | 2ND ELECTRICAL PLAN REVIEW |
| | |
| | APPLICABLE CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70- 2011 |
| | PREVIOUS COMMENT NOT ADDRESSED: |
| | |
| | 8. PER NEC 220.87 PROVIDE 1 YEAR MAXIMUM DEMAND DATA |
| | REPORT TO VERIFY IF EXISTING SERVICE IS SUFFICIENT TO |
| | CARRY NEW SERVICE ADDED. |
| | COMMENTS: |
| | |
| | 1. LABEL ALL MAINS 1OF5, 2OF5 ETC. NEC 230.71 |
| | 2. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO |
| | INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC |
| | 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE |
| | VERBIAGE IN CODE. |
| | 3. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE |
| | TO CONTACT ME SHOULD YOU HAVE ANY |
| | |
| | |
| | VALENTINO PEREZ |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6717 |
| | [email protected] |
| | |
| 2016-08-30 14:00:56 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | PROJECT NAME: OLAOLU REAL ESTATE |
| | JOB ADDRESS: 2580 METRO CENTRE BLVD. |
| | DESCRIPTION: INTERIOR RENOVATION |
| | MASTER PERMIT: 16081034 |
| | |
| | BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS. |
| | ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF |
| | SUBMITTED CORRECTIONS. |
| | |
| | 1. NEC 600.5 STATES THAT EACH COMMERCIAL BUILDING AND |
| | EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO PEDESTRIANS |
| | SHALL BE PROVIDED WITH AT LEAST ONE 20 AMP DEDICATED |
| | OUTLET IN AN ACCESSIBLE LOCATION AT EACH ENTRANCE TO |
| | EACH TENANT SPACE FOR SIGN OR OUTLINE LIGHTING. SERVICE |
| | HALLWAYS OR CORRIDORS SHALL NOT BE CONSIDERED |
| | ACCESSIBLE TO PEDESTRIANS. I DO NOT SEE THIS ON ANY OF |
| | THE DOORS ON EITHER THE POWER OR LIGHTING PLAN. |
| | 2. NEC 210.62 CALLS FOR AT LEAST ONE RECEPTACLE OUTLET |
| | TO BE INSTALLED WITHIN 18? OF THE TOP OF A SHOW WINDOW |
| | FOR EVERY 12 LINEAR FT. OR MAJOR PORTION THEREOF AREA |
| | MEASURED HORIZONTALLY. THIS APPLIES TO THE STORE FRONT |
| | AREAS OF THIS BLDG. |
| | 3. ROOMS 136, 142, 145, 150, 158, 159, 160 & 161 SHALL |
| | COMPLY WITH NEC 517 PART III. |
| | 4. AUTOMATIC CONTROL FOR RECEPTACLES AS INDICATED IN |
| | FBC-E 405.7.1 IS REQUIRED. |
| | 5. DISCONNECTS CONFORMING WITH NEC 440.12 IS REQUIRED |
| | FOR THE CONDENSING UNITS. |
| | 6. NEC 314.27(D): BOXES USED FOR THE SOLE SUPPORT OF |
| | CEILING FANS SHALL BE MARKED BY THE MANUFACTURER AS |
| | SUITABLE FOR THE PURPOSE, AND INDICATE THE WEIGHT |
| | LIMITATIONS BUT SHALL NOT BE USED TO SUPPORT PADDLE |
| | FANS HEAVIER THAN 70 LBS. |
| | 7. EMERGENCY LIGHTING IS REQUIRED FOR THE ROOMS |
| | MENTIONED ABOVE IN COMMENT #3. |
| | 8. PROVIDE MAXIMUM DEMAND DATA FOR 1 YEAR AS REQUIRED |
| | BY NEC 220.87 TO DETERMINE THAT THE EXISTING SERVICE IS |
| | CAPABLE OF ABSORBING THE ADDED DEMAND. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |