| Date |
Text |
| 2016-09-23 12:15:06 | 1ST REVIEW |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER LL |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 561-805-6711 |
| | [email protected] |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1.SHOW ACCESSIBILITY COMPLIANCE FOR SHOWERS TO COMPLY |
| | WITH FBC ACC |
| | 608.3 GRAB BARS. |
| | GRAB BARS SHALL COMPLY WITH 609 AND SHALL BE PROVIDED |
| | IN ACCORDANCE WITH 608.3. WHERE MULTIPLE GRAB BARS ARE |
| | USED, REQUIRED HORIZONTAL GRAB BARS SHALL BE INSTALLED |
| | AT THE SAME HEIGHT ABOVE THE FINISH FLOOR. |
| | 608.3.1 TRANSFER TYPE SHOWER COMPARTMENTS. |
| | IN TRANSFER TYPE COMPARTMENTS, GRAB BARS SHALL BE |
| | PROVIDED ACROSS THE CONTROL WALL AND BACK WALL TO A |
| | POINT 18 INCHES (455 MM) FROM THE CONTROL WALL. |
| | 608.3.2 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS. |
| | WHERE A SEAT IS PROVIDED IN STANDARD ROLL-IN TYPE |
| | SHOWER COMPARTMENTS, GRAB BARS SHALL BE PROVIDED ON THE |
| | BACK WALL AND THE SIDE WALL OPPOSITE THE SEAT. GRAB |
| | BARS SHALL NOT BE PROVIDED ABOVE THE SEAT. WHERE A SEAT |
| | IS NOT PROVIDED IN STANDARD ROLL-IN TYPE SHOWER |
| | COMPARTMENTS, GRAB BARS SHALL BE PROVIDED ON THREE |
| | WALLS. GRAB BARS SHALL BE INSTALLED 6 INCHES (150 MM) |
| | MAXIMUM FROM ADJACENT WALLS. |
| | 608.5.1 TRANSFER TYPE SHOWER COMPARTMENTS. |
| | IN TRANSFER TYPE SHOWER COMPARTMENTS, THE CONTROLS, |
| | FAUCETS, AND SHOWER SPRAY UNIT SHALL BE INSTALLED ON |
| | THE SIDE WALL OPPOSITE THE SEAT 38 INCHES (965 MM) |
| | MINIMUM AND 48 INCHES (1220 MM) MAXIMUM ABOVE THE |
| | SHOWER FLOOR AND SHALL BE LOCATED ON THE CONTROL WALL |
| | 15 INCHES (380 MM) MAXIMUM FROM THE CENTERLINE OF THE |
| | SEAT TOWARD THE SHOWER OPENING. |
| | 608.5.1 TRANSFER TYPE SHOWER COMPARTMENTS. |
| | IN TRANSFER TYPE SHOWER COMPARTMENTS, THE CONTROLS, |
| | FAUCETS, AND SHOWER SPRAY UNIT SHALL BE INSTALLED ON |
| | THE SIDE WALL OPPOSITE THE SEAT 38 INCHES (965 MM) |
| | MINIMUM AND 48 INCHES (1220 MM) MAXIMUM ABOVE THE |
| | SHOWER FLOOR AND SHALL BE LOCATED ON THE CONTROL WALL |
| | 15 INCHES (380 MM) MAXIMUM FROM THE CENTERLINE OF THE |
| | SEAT TOWARD THE SHOWER OPENING. |
| | 608.4 SEATS. |
| | A FOLDING OR NON-FOLDING SEAT SHALL BE PROVIDED IN |
| | TRANSFER TYPE SHOWER COMPARTMENTS. A FOLDING SEAT SHALL |
| | BE PROVIDED IN ROLL-IN TYPE SHOWERS REQUIRED IN |
| | TRANSIENT LODGING GUEST ROOMS WITH MOBILITY FEATURES |
| | COMPLYING WITH 806.2. SEATS SHALL COMPLY WITH 610. |
| | 610.3 SHOWER COMPARTMENT SEATS. |
| | WHERE A SEAT IS PROVIDED IN A STANDARD ROLL-IN SHOWER |
| | COMPARTMENT, IT SHALL BE A FOLDING TYPE, SHALL BE |
| | INSTALLED ON THE SIDE WALL ADJACENT TO THE CONTROLS, |
| | AND SHALL EXTEND FROM THE BACK WALL TO A POINT WITHIN 3 |
| | INCHES (75 MM) OF THE COMPARTMENT ENTRY. WHERE A SEAT |
| | IS PROVIDED IN AN ALTERNATE ROLL-IN TYPE SHOWER |
| | COMPARTMENT, IT SHALL BE A FOLDING TYPE, SHALL BE |
| | INSTALLED ON THE FRONT WALL OPPOSITE THE BACK WALL, AND |
| | SHALL EXTEND FROM THE ADJACENT SIDE WALL TO A POINT |
| | WITHIN 3 INCHES (75 MM) OF THE COMPARTMENT ENTRY. IN |
| | TRANSFER-TYPE SHOWERS, THE SEAT SHALL EXTEND FROM THE |
| | BACK WALL TO A POINT WITHIN 3 INCHES (75 MM) OF THE |
| | COMPARTMENT ENTRY. THE TOP OF THE SEAT SHALL BE 17 |
| | INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM |
| | ABOVE THE BATHROOM FINISH FLOOR. SEATS SHALL COMPLY |
| | WITH 610.3.1 OR 610.3.2. |
| | 610.3.1 RECTANGULAR SEATS. |
| | THE REAR EDGE OF A RECTANGULAR SEAT SHALL BE 2 1/2 |
| | INCHES (64 MM) MAXIMUM AND THE FRONT EDGE 15 INCHES |
| | (380 MM) MINIMUM AND 16 INCHES (405 MM) MAXIMUM FROM |
| | THE SEAT WALL. THE SIDE EDGE OF THE SEAT SHALL BE 11/2 |
| | INCHES (38 MM) MAXIMUM FROM THE ADJACENT WALL. |
| | 610.3.2 L-SHAPED SEATS. |
| | THE REAR EDGE OF AN L-SHAPED SEAT SHALL BE 2 1/2 INCHES |
| | (64 MM) MAXIMUM AND THE FRONT EDGE 15 INCHES (380 MM) |
| | MINIMUM AND 16 INCHES (405 MM) MAXIMUM FROM THE SEAT |
| | WALL. THE REAR EDGE OF THE ?L? PORTION OF THE SEAT |
| | SHALL BE 11/2 INCHES (38 MM) MAXIMUM FROM THE WALL AND |
| | THE FRONT EDGE SHALL BE 14 INCHES (355 MM) MINIMUM AND |
| | 15 INCHES (380 MM) MAXIMUM FROM THE WALL. THE END OF |
| | THE ?L? SHALL BE 22 INCHES (560 MM) MINIMUM AND 23 |
| | INCHES MAXIMUM (585 MM) FROM THE MAIN SEAT WALL. |
| | |
| | 2. SHOW CLEAR FLOOR SPACE FOR SHOWERS . PER FBC ACC . |
| | 608.2.1 TRANSFER TYPE SHOWER COMPARTMENTS. |
| | TRANSFER TYPE SHOWER COMPARTMENTS SHALL BE 36 INCHES |
| | (915 MM) BY 36 INCHES (915 MM) CLEAR INSIDE DIMENSIONS |
| | MEASURED AT THE CENTER POINTS OF OPPOSING SIDES AND |
| | SHALL HAVE A 36 INCH (915 MM) WIDE MINIMUM ENTRY ON THE |
| | FACE OF THE SHOWER COMPARTMENT. CLEARANCE OF 36 INCHES |
| | (915 MM) WIDE MINIMUM BY 48 INCHES (1220 MM) LONG |
| | MINIMUM MEASURED FROM THE CONTROL WALL SHALL BE |
| | PROVIDED. |
| | 608.2.2 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS. |
| | STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS SHALL BE 30 |
| | INCHES (760 MM) WIDE MINIMUM BY 60 INCHES (1525 MM) |
| | DEEP MINIMUM CLEAR INSIDE DIMENSIONS MEASURED AT CENTER |
| | POINTS OF OPPOSING SIDES AND SHALL HAVE A 60 INCHES |
| | (1525 MM) WIDE MINIMUM ENTRY ON THE FACE OF THE SHOWER |
| | COMPARTMENT. |
| | |
| | 3. SHOWER IN STAFF TOILET RM 118 SHALL BE 36" X 36" PER |
| | FBC ACC 608.2.1 |
| | |
| | 4. SHOW ACCESSIBILITY COMPLIANCE FOR WATER FOUNTAIN FBC |
| | ACC |
| | 602.2 CLEAR FLOOR SPACE. |
| | UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE |
| | COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH |
| | AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED. |
| | 602.4 SPOUT HEIGHT. |
| | SPOUT OUTLETS SHALL BE 36 INCHES (915 MM) MAXIMUM ABOVE |
| | THE FINISH FLOOR OR GROUND. |
| | |
| | 5.. A SERVICE SINK IS REQUIRED PER FBC PL TABLE 403.1 |
| | |
| | 6. ALL PUBLIC LAVATORY'S SHALL HAVE TEMPERED WATER |
| | SHALL BE DELIVERED BY A TEMPERATURE LIMITING DEVICE. |
| | PER FBC PL |
| | 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING |
| | FACILITIES. |
| | TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND |
| | GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES |
| | PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED |
| | WATER SHALL BE DELIVERED THROUGH AN APPROVED |
| | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| | 1070 OR CSA B125.3. |
| | |
| | 607.1.1 TEMPERATURE LIMITING MEANS. |
| | A THERMOSTAT CONTROL FOR A WATER HEATER SHALL NOT SERVE |
| | AS THE TEMPERATURE LIMITING MEANS FOR THE PURPOSES OF |
| | COMPLYING WITH THE REQUIREMENTS OF THIS CODE FOR |
| | MAXIMUM ALLOWABLE HOT OR TEMPERED WATER DELIVERY |
| | TEMPERATURE AT FIXTURES. |
| | |
| | 7. SHT. P-5 DETAIL FOR WATER HEATER SHOWS PAN DRAIN |
| | INTO A MOP SINK ONLY THERE'S NO MOP SINK. THIS SIZE |
| | HEATER WOULD HAVE TO BE ON A PLATFORM IN ORDER TO DRAIN |
| | INTO ANY KIND OF MOP SINK OR FLOOR SINK . PLEASE |
| | CLARIFY SHALL COMPLY WITH |
| | FBC PL 504.7.2 PAN DRAIN TERMINATION. |
| | THE PAN DRAIN SHALL EXTEND FULL-SIZE AND TERMINATE OVER |
| | A SUITABLY LOCATED INDIRECT WASTE RECEPTOR OR FLOOR |
| | DRAIN OR EXTEND TO THE EXTERIOR OF THE BUILDING AND |
| | TERMINATE NOT LESS THAN 6 INCHES (152 MM) AND NOT MORE |
| | THAN 24 INCHES (610 MM) ABOVE THE ADJACENT GROUND |
| | SURFACE. |
| | |
| | 8. SHT. P-3 THE 3" SANITARY PIPE CONNECTING THE STAFF |
| | TOILET ROOM 118 AND THE 2 SINKS SHALL CONNECT DOWN |
| | STREAM OF THE ADA TOILET ROOM 113. PER FBC 912.1 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |