| Plan Review Notes For Permit 16081034 |
| Permit Number |
16081034 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-08-30 16:38:32 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #16081034 | | | 8/30/16 | | | | | | 1) THE SELECTED AC SYSTEMS ARE OVERSIZED IN COOLING AND | | | HEATING CAPACITIES PER THE SUBMITTED WHOLE AREA | | | CALCULATION- REFER TO SECTION C403.2.2 FBC-14 ENERGY | | | CONSERVATION. | | | | | | 2) DUCT SMOKE DETECTORS ARE REQUIRED IN THE RETURN AIR | | | SYSTEMS OF AHU'S #1-6 PER SECTION 606.2.1. THIS | | | REQUIREMENT MAY BE WAIVED IF MANUFACTURER'S | | | SPECIFICATIONS INDICATE THE UNITS DO NOT HAVE THE | | | CAPACITY TO PRODUCE OVER 2000 CFMS EACH. | | | | | | 3) EXHAUST VENTILATION IS REQUIRED FOR THE LAB AND | | | RECIRCULATION OF THE AIR IS PROHIBITED EXCEPT WHERE THE | | | RESULTING AIR STREAM CONSISTS OF NOT MORE THAN 10% AIR | | | RECIRCULATED FROM THE SPACE- SEE TABLE 403.3 AND | | | FOOTNOTE G. | | | | | | 4 ) REFER TO TABLE 403.3 AND PROVIDE COMPLETE | | | VENTILATION CALCULATIONS FOR THE PROPOSED OCCUPANCY | | | INCLUDING THE EXAM ROOMS, THE INFUSION ROOM, THE LAB, | | | THE PHARMACY, THE STORAGE ROOMS, AND CORRIDORS. | | | | | | 5) PROVIDE CONDENSATE DISPOSAL DETAILS FOR AHU #5. | | | | | | 6) PROVIDE EQUIPMENT SCHEDULES FOR THE MOTORIZED | | | DAMPERS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|