| 2016-09-01 14:11:10 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THERE IS NO INDICATION OF COMPLIANCE WITH A FIRE |
| | CODE. |
| | |
| | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| | THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| | APPLICABLE CODES OR STANDARDS. |
| | |
| | PLEASE REVIEW, ENSURE COMPLAINCE AND PROVIDE THE |
| | APPLICABLE NOTE. |
| | |
| | |
| | 2) THERE IS NO INDICATION OF THE PROPOSED OCCUPANCY |
| | CLASSIFICATION. |
| | |
| | NFPA 1 |
| | |
| | CHAPTER 6 CLASSIFICATION OF OCCUPANCY |
| | 6.1 CLASSIFICATION OF OCCUPANCY. |
| | 6.1.1 GENERAL. |
| | 6.1.1.1 OCCUPANCY CLASSIFICATION. THE OCCUPANCY OF A |
| | BUILDING OR STRUCTURE, OR PORTION OF A BUILDING OR |
| | STRUCTURE, SHALL BE CLASSIFIED IN ACCORDANCE WITH 6.1.2 |
| | THROUGH 6.1.13. OCCUPANCY CLASSIFICATION SHALL BE |
| | SUBJECT TO THE RULING OF THE AHJ WHERE THERE IS A |
| | QUESTION OF PROPER CLASSIFICATION IN ANY INDIVIDUAL |
| | CASE. [101:6.1.1.1] |
| | |
| | PLEASE PROVIDE DETAILS AS TO THE NATURE OF THE PROJECT |
| | BUSINESS AND THE OCCUPANCY CLASSIFICATION. |
| | |
| | |
| | 3) PLEASE PROVIDED A COMPLETE LIFE SAFETY PLAN THAT |
| | ILLUSTRATES OCCUPANT LOADS, TRAVEL DISTANCES, COMMON |
| | PATHS OF TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS, |
| | EMERGENCY LIGHTING, SITE PLAN ENSURING EXITS LEAD TO A |
| | PUBLIC WAY, AND FIRE EXTINGUISHER LOCATIONS. ALL IN |
| | ACCORDANCE WITH THE REQUIRERMENTS OF THE FLORIDA FIRE |
| | PREVENTION CODE, 5TH EDITION. |
| | |
| | |
| | 4) THERE IS NO INDICATION OF ANY EXSITING OR PROPOSED |
| | LIFE SAFETY SYSTEMS, I.E. FIRE ALARM AND FIRE |
| | SPRINKLER. |
| | |
| | PLEASE PROVIDE NOTE OF EITHER IS EXISITNG. |
| | |
| | IF NEW SYSTEMS ARE PROPOSED PLEASE INCLUDE 61G REQUIRED |
| | INFO OR DRAWINGS. |
| | |
| | |
| | 5) PLEASE PROVIDE PLAN SHEET REVISION CLOUDS OR |
| | NUMBERED NARRATIVE RESPONSES TO THE ABOVE. |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |