| 2016-09-12 14:35:38 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16081034 |
| | ADD: 2580 METROCENTRE BLVD. SUITE 3, 4 & 5 |
| | CONT: ANDERSON MOORE CONSTRUCTION |
| | TEL: 753-7400 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: |
| | ACTION: DENIED |
| | |
| | 1) WITHIN THE SET OF PLANS THERE IS NO PLAN WITH |
| | PROJECT INFORMATION, CODE ANALYSIS AND LIFE SAFETY |
| | PLAN. |
| | 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1: |
| | |
| | ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR |
| | BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS/ 107.3.5.1.1 BUILDING: |
| | OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| | SHALL BE DETERMINED. |
| | MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE |
| | TABLE 503). PROVIDE SQUARE FOOTAGE OF BUILDING. |
| | FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL INCLUDE |
| | THE FOLLOWING COMPONENTS: |
| | FIRE-RESISTANT SEPARATIONS |
| | FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION |
| | FIRE SUPPRESSION SYSTEMS REQUIRED? YES OR NO, THEY |
| | SHALL INCLUDE: |
| | SCHEMATIC FIRE SPRINKLERS/ PRE-ENGINEERED SYSTEMS |
| | LIFE SAFETY PLAN SHALL INCLUDE THE FOLLOWING |
| | REQUIREMENTS: |
| | OCCUPANT LOAD AND EGRESS CAPACITIES |
| | OCCUPANCY LOAD |
| | GROSS |
| | NET |
| | MEANS OF EGRESS |
| | EXIT ACCESS |
| | EXIT |
| | EXIT DISCHARGE |
| | DOORS |
| | EMERGENCY LIGHTING AND EXIT SIGNS |
| | ACCESSIBILITY REQUIREMENTS SHALL INCLUDE ACCESS CODE |
| | SIGNS SHALL BE PROVIDED IN ACCORDANCE WITH 216 AND |
| | SHALL COMPLY WITH 703. |
| | |
| | 2) SINCE THERE IS NO CODE INFORMATION PROVIDED NO LIFE |
| | SAFETY PLAN FOR WHICH WAY THE OCCUPANTS WILL BE |
| | TRAVELING TO REACH AN EXIT NOR THE QUANTITY OF |
| | OCCUPANTS EACH CORRIDOR WILL BE HANDLING COMPLIANCE |
| | CANNOT BE DETERMINED FOR 2014 FBC-B TABLE 1018.1 |
| | BUSINESS CORRIDORS WITH AN OCCUPANT LOAD GREATER THAN |
| | 30 IN A NON-SPRINKLERED BUILDING WOULD REQUIRE 1 HOUR |
| | FIRE RATED CORRIDORS AND OPENING PROTECTIVES IN |
| | ACCORDANCE WITH FBC-B TABLE 716.5. |
| | 3) SHEET A-1 SHOWS THE TENANT SPACE IS APPROXIMATELY |
| | 8,500 SQUARE FEET IN AREA AND APPEARS TO BE A MIXED USE |
| | OCCUPANCY BETWEEN A BUSINESS AND A2/A3 ASSEMBLY |
| | OCCUPANCY OF APPROXIMATELY 1,150 SQ. FT. WHICH IS OVER |
| | 10 % OF THE TENANT FLOOR AREA. THE DESIGNER OF RECORD |
| | WILL NEED TO IDENTIFY HOW THE MIXED USE OCCUPANCY IS |
| | GOING TO BE CLASSIFIED? AS SEPARATED UNDER 508.3.3 OR |
| | NONSEPARATED OCCUPANCIES UNDER 508.3. |
| | |
| | 4) THERE ARE NO SECTIONS FOUND ON SHEET A1 FOR AN |
| | ACCESSIBLE FRONT OFFICE CHECK IN NOR ANY FOR CHECKING |
| | OUT. FBC-ACCESS. CODE 902.3 HEIGHT. THE TOPS OF WORK |
| | SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND 34 |
| | INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR |
| | GROUND. 904.3.3 CHECK WRITING SURFACES. |
| | WHERE PROVIDED, CHECK WRITING SURFACES SHALL COMPLY |
| | WITH 902.3. |
| | |
| | 5A) SHEET A1 THE STAFF SHOWER IN THE BATHROOM 118 |
| | MEASURES 38 X38 INCHES. PLEASE PROVIDE COMPLIANCE WITH |
| | THE ACCESS. CODE FOR THE REQUIRED SIZE 36 X 36 INCHES |
| | SEE 608.2. |
| | |
| | 5B) THE PLAN DOES NOT SHOW THE CONTROL VALVE WALL NOR |
| | THE SEAT WALL NOR REQUIRED CLEARANCES. SEE ACCESS. CODE |
| | 608.2.1 AND FIGURE 608.2.1. PLEASE ALSO PROVIDE |
| | COMPLIANCE FOR GRAB BAR PLACEMENT SEE SECTION 608.3 AND |
| | FIGURE 608.3.1 AND CONTROLS FIGURE 608.5.1. |
| | |
| | 6) SHEET A1 WILL ALSO NEED TO SHOW COMPLIANCE FOR THE A |
| | SHOWER IN THE BATHROOM 113 FOR A STANDARD ROLL IN |
| | SHOWER IN COMPLIANCE WITH 608.3.2, & 608.6. |
| | |
| | 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |