| 2016-08-30 17:57:47 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | PROJECT NAME: REMODEL OF EXISTING STRUCTURE |
| | JOB ADDRESS: 727 22ND ST. |
| | DESCRIPTION: REMODEL OF EXISTING STRUCTURE TO INCLUDE |
| | MEP, STRUCTURE, FRAMING, DRYWALL, ROOFING FLOORING AND |
| | CABINETRY |
| | MASTER PERMIT: 16081001 |
| | |
| | BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS. |
| | ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF |
| | SUBMITTED CORRECTIONS. ITEMS 1 & 2 BELOW CAN BE |
| | ADDRESSED WITH A BLOCK NOTE. |
| | |
| | 1. UNIT 1 IS MISSING THE REQUIRED LIGHT OUTSIDE OF THE |
| | REAR DOOR. THIS MAY BE AN OVERSIGHT AS THE SWITCH FOR |
| | SAME IS DRAWN ON THE PLANS. |
| | 2. FBC-RE4002.9/NEC 406.9(B) RECEPTACLES IN WET |
| | LOCATIONS. 15 AND 20 AMPERE, 125 AND 250 VOLT |
| | RECEPTACLES INSTALLED IN A WET LOCATION SHALL HAVE AN |
| | ENCLOSURE THAT IS WEATHERPROOF WHETHER OR NOT THE |
| | ATTACHMENT PLUG CAP IS INSERTED. ALL 15 AND 20 AMPERE, |
| | 125 AND 250 VOLT NONLOCKING RECEPTACLES SHALL BE LISTED |
| | WEATHER-RESISTANT TYPE ?WR?. |
| | 3. FBC-RE3905.6.2/NEC 314.27(A) LUMINAIRE OUTLETS. |
| | BOXES USED AT LUMINAIRE OR LAMPHOLDER OUTLETS IN A |
| | CEILING SHALL BE REQUIRED TO SUPPORT A LUMINAIRE |
| | WEIGHING A MINIMUM OF 50 LB. ADD THIS TO THE NOTES ON |
| | CEILING BOXES ON PAGE. |
| | 4. FBC-RE3703.3/NEC 210.50(E) LAUNDRY CIRCUIT. A |
| | MINIMUM OF ONE 20-AMPERERATED BRANCH CIRCUIT SHALL BE |
| | PROVIDED FOR RECEPTACLES LOCATED IN THE LAUNDRY AREA |
| | AND SHALL SERVE ONLY RECEPTACLE OUTLETS LOCATED IN THE |
| | LAUNDRY AREA. THE ELECTRICAL CODE DOES NOT SAY THAT A |
| | WASHER HAS TO BE PROVIDED BUT IT DOES REQUIRE THAT AN |
| | OUTLET FOR THE UNIT BE INSTALLED AND INCLUDED IN THE |
| | LOAD CALCS FOR EACH DWELLING. |
| | 5. FBC-RE3903.4/NEC 210.70(A)(3) STORAGE OR EQUIPMENT |
| | SPACES. AT LEAST ONE LIGHTING OUTLET CONTAINING A |
| | SWITCH OR CONTROLLED BY A WALL SWITCH SHALL BE |
| | INSTALLED WHERE THESE SPACES ARE USED FOR STORAGE OR |
| | CONTAIN EQUIPMENT REQUIRING SERVICING. THE LIGHTING |
| | OUTLET SHALL BE PROVIDED AT OR NEAR THE EQUIPMENT |
| | REQUIRING SERVICING. I MAY SUGGEST THAT THIS SWITCH |
| | HAVE A PILOT LIGHT TO INDICATE WHEN THE LIGHT HAS |
| | INADVERTENTLY LEFT ON. |
| | 6. NEC 215.5 DIAGRAMS OF FEEDERS. A RISER DIAGRAM |
| | SHOWING FEEDER DETAILS ALONG WITH RESPECTIVE LOAD CALCS |
| | SHALL BE PROVIDED. THIS DIAGRAM SHALL INCLUDE CONDUCTOR |
| | SIZING AND INSULATION TYPE. FURTHERMORE, IT SHALL BE |
| | SITE SPECIFIC. |
| | 7. FBC-RE3706.3/NEC 408.36 PANELBOARD OVERCURRENT |
| | PROTECTION. IN ADDITION TO THE REQUIREMENT OF SECTION |
| | E3706.1, A PANELBOARD SHALL BE PROTECTED BY AN |
| | OVERCURRENT PROTECTIVE DEVICE HAVING A RATING NOT |
| | GREATER THAN THAT OF THE PANELBOARD. SUCH OVERCURRENT |
| | PROTECTIVE DEVICE SHALL BE LOCATED WITHIN OR AT ANY |
| | POINT ON THE SUPPLY SIDE OF THE PANELBOARD. INDICATE IF |
| | THE PROPOSED PANELS ARE MCB OR MLO AND THE OVERCURRENT |
| | PROTECTION IS INTEGRAL TO THE METER CENTER. |
| | 8. THE PANELS ARE INCORRECTLY LABELED ON THE FLOOR |
| | PLAN. THESE UNITS ARE SIDE BY SIDE AND THE PANELS AND |
| | METER SHALL BE MARKED TO INDICATE WHICH UNIT THEY |
| | BELONG TO. |
| | 9. FBC-ER3609.3/NEC 250.94 BONDING FOR OTHER SYSTEMS. |
| | THE INTER-SYSTEM BONDING TERMINAL PRESCRIBED SHALL BE |
| | INSTALLED. |
| | 10. FBC-ER404.1 LIGHTING EQUIPMENT (MANDATORY). A |
| | MINIMUM OF 75 PERCENT OF THE LAMPS IN PERMANENTLY |
| | INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY |
| | LAMPS OR A MINIMUM OF 75 PERCENT OF THE PERMANENTLY |
| | INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH |
| | EFFICACY LAMPS. |
| | |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |