2016-08-30 11:39:54PERMIT # 16080989
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PASSED PROVISO:
  
 1) SHEET 2: UNIT A.1R NEEDS TO BE REVIEWED FOR ADEQUATE
 SPRINKLER COVERAGE BETWEEN THE LIVING ROOM AND DINING
 ROOM. THERE IS A SPACE THAT IS NOT PROTECTED BY EITHER
 SIDEWALL BECAUSE OF IT'S LOCATION INDENTED IN THE
 LIVING ROOM.
 CIRCLED IN BLUE PEN.)
  
 2) SPRINKLERS ARE NOT INCLUDED IN THE COMMON CORRIDOR/
 CENTER HALLWAY BETWEEN THE APARTMENTS. PLEASE PROVIDE
 THE CODE REFERENCE THAT ALLOWS FOR THIS OMISSION IN
 SPRINKLER PROTECTION.
 IF SPRINKLER HEADS WILL BE ADDED TO THE HALLWAYS, A
 REVISION WILL NEED TO BE SUBMITTED PRIOR TO THE FIRST
 INSPECTION.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  