| 2016-09-06 10:31:22 | 2ND REVIEW FBC-2014 MECHANICAL |
| | PERMIT #16080985 |
| | 9/6/16 |
| | |
| | COMMENTS FROM THE 1ST REVIEW (PRINTED BELOW ) WITH THE |
| | EXCEPTION OF #6 STILL EXIST. ASTRO AIR'S TITLE BLOCK |
| | HAS BEEN REMOVED FORM THE NEW PLANS HOWEVER, NO |
| | SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN IS |
| | SHOWN ON THE NEW PLANS |
| | |
| | 1) THE SELECTED AC SYSTEM SHOWN ON THE PLAN IS A |
| | GOODMAN PACKAGED UNIT SUITABLE FOR OUTDOOR USE ONLY. |
| | THE ORIGINAL APPROVED PLAN (PERMIT #16020067) CALLED |
| | FOR REPLACEMENT OF A WATER COOLED HEAT PUMP. IT APPEARS |
| | THAT THE NEW AC INFORMATION IS A MISTAKE, HOWEVER IF |
| | THE PACKAGED UNIT IS TO BE INSTALLED, PLEASE PROVIDE |
| | THE FOLLOWING DETAILS ON THE PLAN: A) SHOW THE LOCATION |
| | OF THE PROPOSED UNIT AND PROVIDE INSTALLATION DETAILS |
| | INCLUDING WIND LOAD ENGINEERING PER SECTION 301.15. B) |
| | PROVIDE A REVISED DUCT LAYOUT PLAN THAT SHOWS THE MAIN |
| | SUPPLY AND RETURN CONNECTIONS TO THE UNIT. C) PROVIDE A |
| | CONDENSATE DISPOSAL PLAN. |
| | |
| | 2) THIS REVISED PLAN APPEARS TO BE REPLACING THE |
| | ORIGINAL PLAN SUBMITTED UNDER #16020067, HOWEVER SOME |
| | OF THE INFORMATION ON THE ORIGINAL HAS NOT BEEN PLACED |
| | ON THE REVISED PLAN, AND NO CLOUDS OR DELTA SYMBOLS ARE |
| | SHOWN ON THE DRAWINGS TO HIGHLIGHT THE CHANGES. PLEASE |
| | PROVIDE A COMPLETELY REVISED PLAN. |
| | |
| | 3) PROVIDE THE SIZE OF THE NEW DUCT IN THE LIVING ROOM, |
| | AND THE DUCT SIZES IN THE BEDROOMS CONNECTING THE NEW |
| | DIFFUSERS. |
| | |
| | 4) PROVIDE A MEANS OF RETURN AIR FROM THE BEDROOMS. |
| | |
| | 5) FLORIDA ENERGY CONSERVATION CODE-2014: PLEASE REVIEW |
| | SECTIONS C403.2.7.2 FOR MECHANICAL CLOSET REQUIREMENTS, |
| | AND SECTION C403.2.7.3.3 FOR REQUIRED SPACE AROUND THE |
| | AIR HANDLER IN THE MECHANICAL CLOSET. REVISE THE PLANS |
| | ACCORDINGLY. |
| | |
| | 6) PLEASE REMOVE THE ASTROAIR TITLE BLOCK FROM THE PLAN |
| | IF THEY ARE NOT THE CONTRACTOR ON THE PROJECT. REFER TO |
| | SECTION 107.2.1 WPB AMENDMENTS TO THE FBC: THE |
| | SUBMITTED PLAN SHALL BEAR THE SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |