| 2016-08-24 13:29:50 | BUILDING PLAN REVIEW | | | 2014 FLORIDA BUILDING CODE | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER ? PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | DEVELOPMENT SERVICES DEPARTMENT | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | DATE: 8/24/16 | | | | | | 1. PLEASE PROVIDE ASTM E-84 (FLAME SPREAD), E-90 (SOUND | | | TRANSMISSION) AND E-492 (IMPACT SOUND) REPORTS FOR THE | | | PREVAIL UNDERLAYMENT TO BE USED. | | | | | | FBC 603.1 FLAME SPREAD ? ASTM E-84 | | | | | | FBC 1207.2 AIR-BORNE SOUND. ASTM E - 09-02 | | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E 90. | | | | | | FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E - 492-04 | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. | | | | | | | | | |
|