| Plan Review Notes For Permit 16080974 |
| Permit Number |
16080974 |
|
| Review Stop |
M |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2017-01-03 10:33:30 | 5TH REVIEW FBC-2014 MECHANICAL | | | PERMIT #16080974 | | | 1/3/17 | | | | | | 1) COMMENTS FROM THE PREVIOUS REVIEWS REGARDING MAKEUP | | | TEMPERATURE STILL EXISTS. IF CHOOSING TO SHOW THAT THE | | | EXISTING OR PROPOSED AC SYSTEM HAS THE CAPACITY TO | | | ACCOMODATE THE ADDITIONAL HEAT GAIN FROM THE MAKEUP | | | AIR, PLEASE PROVIDE AN EQUIPMENT SCHEDULE FOR THE | | | SYSTEM AND A LOAD CALCULATION FOR THE SPACE THAT | | | INCLUDES THE ADDITIONAL HEAT LOAD. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|