| Plan Review Notes For Permit 16080974 |
| Permit Number |
16080974 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-09-19 12:44:25 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #16080974 | | | 9/19/16 | | | | | | 1) SUBMIT THE NOA'S FOR THE FANS. | | | | | | 2) CLARIFY HOW COMPLIANCE IS BEING MET FOR MAKEUP AIR | | | TEMPERATURE- SEE SECTION 508.1.1 FBC-14 MECH. | | | | | | 3) PROVIDE AN ENLARGED DETAIL FOR THE GREASE DUCT | | | ENCLOSURE AT THE ROOF PENETRATION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|