2016-08-30 13:30:49INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PLEASE NOTE THAT PER FBC 105.3.1.2(5)- FLORIDA
 STATUE 471.003(2)(H) AN ELECTRICAL CONTRACTOR CANNOT
 DESIGN ELECTRICAL SERVICE AS VOLTAGE IS ABOVE 240V.
 RISER SHOWS A 3PHASE 240V (480V PHASE TO PHASE. PLANS
 TO BE DESIGN BY ENGINEER FOR THIS PROJECT.
 2. PLEASE SHOW AIC CALCULATION BASED ON INFORMATION
 PROVIDED BY FPL UTILITY FOR APPROVAL. NEC 110.24 FBC
 107. LABEL EQUIPMENT AIC RATINGS.
 3. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO
 INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC
 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE
 VERBIAGE IN CODE.
 4. LABEL SERVICE EQUIPMENT TO BE RATED FOR SERVICE
 ENTRANCE. NEC 230.66
 5. CLARIFY GENERATOR RECEPTACLE SHOWN. WILL THERE BE A
 PERMANENT GENERATOR INSTALLED, PLEASE CLARIFY. FBC
 107.3.5
 6. NEUTRAL CONDUCTOR BROUGHT TO SERVICE IS REDUCED.
 PROVIDE A NEUTRAL CALCULATION REGARDLESS OF LOAD OR
 SHOW UPSIZED.
 7. PROVIDE A WP/GFCI RECEPTACLE AT THE SERVICE. NEC
 590.6
 8. SHOW AN INTERSYSTEM BONDING TERMINAL PER NEC 250.94
 9. SHOW CONDUIT AND CONDUCTOR SIZE TO PUMPS AND FROM
 METER TO MAIN DISCONNECTS. FBC 107.3.5
 10. HIGH LEG MARKINGS TO BE PROVIDED PER NEC 110.15 AND
 408.3F1 PROVIDE NOTE ON RISER DIAGRAM
 11. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL
 FREE TO CONTACT ME SHOULD YOU HAVE ANY
  
  