| 2016-08-30 17:01:16 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | DESCRIPTION: RENO OF EXISTING SPACE TO INCLUDE MEP, |
| | FIRE ALARM & FIRE SPRINKLERS. |
| | |
| | BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS. |
| | ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF |
| | SUBMITTED CORRECTIONS. |
| | |
| | 1. CORRECT LIGHTING FIXTURE SCHEDULE DESCRIPTION FOR F1 |
| | FIXTURE. |
| | 2. CORRECT ELECTRICAL SPECIFICATIONS PART 1 NOTE C TO |
| | READ THE 2011 EDITION OF THE NEC. |
| | 3. CORRECT ELECTRICAL SPECIFICATIONS PART 2 NOTE D. TO |
| | REMOVE SCH 40 LIMITATION AS THERE ARE CONDITIONS WHICH |
| | CALL FOR SCH 80. |
| | 4. CORRECT ELECTRICAL SPECIFICATIONS PART 3 NOTE C TO |
| | READ THE 2011 EDITION OF THE NEC. |
| | 5. PER FBC-EC405.2.1.1 EACH INDIVIDUAL AREA SHALL HAVE |
| | INDEPENDENT MANUAL OVERRIDE AND/OR OCCUPANCY SENSOR. |
| | AREAS 104, 103, 101, 106A, 117, 112, 107, 116 ARE |
| | LACKING THIS. |
| | 6. PER FBC-EC405.2.2.3 DAYLIGHT ZONES SHALL BE |
| | ESTABLISHED AND LIGHTING CONTROLLED INDEPENDENTLY OF |
| | GENERAL AREA LIGHTING. CORRECT LIGHTING LAYOUT |
| | ACCORDINGLY. |
| | 7. NEC 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE |
| | PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE |
| | EQUIPMENT, SWITCHBOARDS, AND PANELBOARDS. THIS LIGHT |
| | SHALL NOT BE CONTROLLED BY AUTOMATIC MEANS ONLY. THIS |
| | PENDANT LIGHT MAY NOT BE AUTOMATICALLY CONTROLLED AND |
| | SHALL BE SUFFICIENT TO PROVIDE AMPLE LIGHTING TO WORK |
| | INSIDE THE ELECTRICAL PANELS. |
| | 8. FBC-E 405.7.1: AT THE LEAST 50% OF ALL 125-VOLT, 15- |
| | AND 20-AMPERE RECEPTACLES SHALL BE AUTOMATICALLY |
| | CONTROLLED WHERE INSTALLED IN PRIVATE OFFICES, OPEN |
| | OFFICES, AND COMPUTER CLASSROOMS. THIS INCLUDES THOSE |
| | INSTALLED IN MODULAR PARTITIONS. (SEE ASHRAE STANDARD |
| | 90.1) |
| | 9. FIRE ALARM WORK SHALL BE COMPLETED UNDER SEPARATE |
| | PERMIT AND SUBMITTAL. |
| | 10. FBC-E 405.7.1: AT THE LEAST 50% OF ALL 125-VOLT, |
| | 15- AND 20-AMPERE RECEPTACLES SHALL BE AUTOMATICALLY |
| | CONTROLLED WHERE INSTALLED IN PRIVATE OFFICES, OPEN |
| | OFFICES, AND COMPUTER CLASSROOMS. THIS INCLUDES THOSE |
| | INSTALLED IN MODULAR PARTITIONS. (SEE ASHRAE STANDARD |
| | 90.1) |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |