| 2016-08-26 13:43:48 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16080942 |
| | ADD: 1551 N. FLAGLER DR. SUITE # CU01 |
| | CONT: BUTLER CONSTRUCTION CO. |
| | TEL: 561-832-9700 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. AUGUST 26/2016 |
| | ACTION: DENIED |
| | |
| | 1) SHEET 002_LS-ALS1.0: |
| | 1A) PLEASE NOTE THE CODE ANALYSIS UNDER THE TYPE OF |
| | CONSTRUCTION LIST THIS AS AN CONSTRUCTION TYPE VB/ |
| | FULLY SPRINKLERED BUILDING. UNDER THE 2014 FBC-B TABLE |
| | 503 FOR A TYPE VB /SPRINKLERED BUILDING WITH THE ONE |
| | STORY INCREASE THIS TENANT SPACE COULD BE IN A 3 STORY |
| | BUILDING. PLEASE NOTE GOOGLE EARTH SHOWS THIS TO BE |
| | WHAT APPEARS TO BE A 14 STORY HIGH-RISE. TABLE 503 FOR |
| | 14 STORY BUILDING FOR A BUSINESS, R2 OR ASSEMBLY |
| | OCCUPANCIES WOULD ALL REQUIRE THIS BUILDING TO BE A |
| | CONSTRUCTION TYPE IA. |
| | |
| | 1B) PLEASE PROVIDE A SURVEY OF THE PROPERTY WITH THE |
| | FLOOD ZONE DELINEATION LINES SHOWN. THE PROPERTY |
| | APPRAISERS WEB SITE SHOWS THEA5 FLOOD DELINEATION LINE |
| | CUTTING THROUGH THE BUILDING. THE CITIES FLOOD MAPS |
| | SHOW THE DELINEATION LINE DEFINITELY ON THE PROPERTY. |
| | IF THE SURVEY SHOWS ANY OF THE BUILDING BEING LOCATED |
| | IN THE A5 FLOOD ZONE THEN FLOOD ELEVATION CERTIFICATES |
| | WILL BE REQUIRED. |
| | |
| | FBC BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES |
| | SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD |
| | ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. |
| | PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS |
| | REQUIRE AN ADDITIONAL 6 INCHES OF ELEVATION. |
| | |
| | DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE |
| | REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES |
| | REQUIRED: |
| | (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE |
| | PLAN REVIEW DOCUMENTS WITH THE PROPOSED |
| | FINISH FLOOR HEIGHT. |
| | (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND |
| | ELEVATION CERTIFICATE IS REQUIRED |
| | (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY |
| | OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD |
| | ZONE CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL |
| | EXTERIOR ATTENDANTS A/C PADS OR OTHER SLABS FOR |
| | GENERATORS |
| | FEMA NEW FORM AVAILABLE JUNE 13/2016. |
| | OMB NO. 1660-0008 |
| | EXPIRATION DATE: NOV. 30/2018 |
| | HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM |
| | |
| | 2) SHEET S1 & S2 SHOW THERE IS STRUCTURAL WORK INVOLVED |
| | AND THIS IS A HIGH-RISE BUILDING MEETING THE DEFINITION |
| | FOR A THRESHOLD BUILDING. THRESHOLD BUILDING / FL S. S. |
| | 553.71(7) ?THRESHOLD BUILDING" MEANING ANY BUILDING |
| | WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, |
| | OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS |
| | DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 |
| | SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN |
| | 500 PERSONS. |
| | |
| | 2A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING |
| | AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL |
| | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| | WITH THE PERMITTED DOCUMENTS. |
| | |
| | 2B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD |
| | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S |
| | 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS |
| | REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS |
| | ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH |
| | INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND |
| | REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE |
| | PLACE. |
| | |
| | 2C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B. |
| | AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH |
| | ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT |
| | OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE |
| | BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE |
| | PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 2D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' |
| | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | |
| | 2E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| | HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| | |
| | 2F) FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, PLEASE |
| | E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING ISSUED, |
| | THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE APPROVED |
| | AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, |
| | TWO SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) |
| | FOR THE THRESHOLD INSPECTOR, THE OTHER FOR THE MEP |
| | INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE IN BLACK |
| | & WHITE.. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD |
| | BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS |
| | CONCERNING SPECIAL INSPECTORS. |
| | |
| | 2G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES, |
| | PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT |
| | AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING |
| | INSTALLATION SHALL BE SUPERVISED, INSPECTED AND |
| | CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING |
| | DOCUMENTS BY THE CONTRACTOR. |
| | |
| | 2H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL |
| | BUILDING INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 |
| | MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. |
| | |
| | 2I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES |
| | FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER |
| | HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE |
| | MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR |
| | WALLS AND CEILINGS. |
| | 3A) THERE ARE ONLY 2 STRUCTURAL SHEETS, 013_S-1 & |
| | 014_S-2. PLEASE NOTE THERE ARE NO DEMOLITION SHEETS |
| | SHOWING WHAT STRUCTURAL MEMBERS ARE BEING REMOVED NOR |
| | HOW WHEN REMOVING THE STRUCTURAL BEAM, HOW TO HANDLE |
| | THE EXISTING BEAM STEEL, IS IT TO BE CUT, IS IT TO BE |
| | SAVED FOR THE PROPER LAPS REQUIRED FOR THE BEAM? ACI |
| | 318 2.7 DEVELOPMENT AND SPLICES OF REINFORCING. |
| | |
| | 3B) THE PLANS ARE SILENT AS TO SHEET 014_S-2 WHERE THE |
| | NEW NANA WALL SYSTEM IS BEING INSTALLED ARE THE |
| | EXTERIOR STAIR AND HANDRAIL/ GUARDRAIL SYSTEMS EXISTING |
| | OR NEW? 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 4) SHEET 013_S-1 UNDER THE WIND DESIGN CRITERIA THE |
| | PLANS LIST THIS AS AN C EXPOSURE, YOU CAN SHOOT A |
| | VECTOR OUT TO THE NNE OVER WATER FOR 5,822 FEET BEFORE |
| | HITTING LAND AND A VECTOR TO THE SSE FOR 6,363 FEET |
| | OVER WATER UNTIL YOU HIT LAND. THIS QUALIFIES THE |
| | EXPOSURE TO BE CONSIDERED AN D EXPOSURE. SEE THE 2014 |
| | FBC-B 1609.4.2 EXPOSURE D. EXPOSURE D SHALL APPLY WHERE |
| | THE GROUND SURFACE ROUGHNESS, AS DEFINED BY SURFACE |
| | ROUGHNESS D, PREVAILS IN THE UPWIND DIRECTION FOR A |
| | DISTANCE OF AT LEAST 5,000 FEET (1524 M) OR 20 TIMES |
| | THE HEIGHT OF THE BUILDING, WHICHEVER IS GREATER. |
| | |
| | 5) PLEASE PROVIDE THE PRESSURES IN VASD SINCE THE |
| | PRODUCT APPROVALS ARE IN VASD. PLEASE NOTE THE |
| | ADJUSTMENT FACTORS TABLE 1609.7.2 FOR HEIGHT AND |
| | EXPOSURE. PRESSURES ARE TO BE TAKEN FROM ASCE 7-10 |
| | SINCE THE BUILDING IS ABOVE 60 FEET IN HEIGHT. |
| | |
| | 6A) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS/ MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, |
| | |
| | 6B) NANA WALL SYSTEM (DOOR) ARE REQUIRED TO BE TESTED |
| | FOR WATER INFILTRATION SEE FBC-B 1710.5.1.1 EXCEPTION # |
| | 2. |
| | |
| | 6C) PLEASE PROVIDE HOW COMPLIANCE WITH THE 2014 ENERGY |
| | CODE C401.2.1/ C402.3. |
| | |
| | 7) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 8) PLEASE NOTE SHEET 022_LS-ALS1.0 SHOWS STEPS UP TO |
| | THE NANA DOOR SYSTEM, THIS IS NOT AN ACCESSIBLE |
| | ENTRANCE, PLEASE PROVIDE SIGNAGE TO THE ACCESSIBLE |
| | ENTRY. 2014 FBC-ACCESSIBILITY CODE 216.3 DIRECTIONAL |
| | AND INFORMATIONAL SIGNS. SIGNS THAT PROVIDE DIRECTION |
| | TO OR INFORMATION ABOUT INTERIOR SPACES AND FACILITIES |
| | OF THE SITE SHALL COMPLY WITH 703.5. |
| | |
| | 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |