| 2016-09-12 10:57:23 | BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 16080940 |
| | W. P. B. PERMIT: 16010466 |
| | ADD: 2400 N FLAGLER DR. CURY PARK/ CITY PUMP/ LIFT |
| | STATION ADDITION & RENOVATION/ ANTENNA TOWER & BASE |
| | BLDG. RISK CATEGORY: IV/ 180 VULT/ MPH |
| | CONT: FLORIDA DESIGN DRILLING CORP. |
| | TEL: 561-844-2966 |
| | E-MAIL: [email protected] |
| | |
| | THE CHAPTER 1 OF THE FLORIDA BUILDING CODE IS AN |
| | ADMINISTRATIVE CODE. WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| | REQUIRES 3 FLOOD ZONE CERTIFICATES, |
| | |
| | (1) WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS |
| | 107.3.5.1.1 BUILDING |
| | (1ST) SITE REQUIREMENTS- FLOOD HAZARD AREAS, FLOOD |
| | ZONES, AND DESIGN FLOOD ELEVATIONS |
| | |
| | PLEASE NOTE THIS FLOOD ELEVATION CERTIFICATE IS |
| | REQUIRED AS PART OF THE PLAN REVIEW REQUIREMENTS, THIS |
| | IS A PROPOSED ELEVATION HEIGHTS AND MARKED ON THE |
| | ELEVATION CERTIFICATE LINE C1. CONSTRUCTION DRAWINGS. |
| | |
| | (2ND) ELEVATION CERTIFICATE REQUIRED. 110.3 REQUIRED |
| | INSPECTIONS. |
| | A. BUILDING |
| | 1. FOUNDATION |
| | 1.2. IN FLOOD HAZARD AREAS, UPON PLACEMENT OF THE |
| | LOWEST FLOOR, INCLUDING BASEMENT, |
| | AND PRIOR TO FURTHER VERTICAL CONSTRUCTION, THE |
| | ELEVATION CERTIFICATION, REQUIRED IN |
| | SECTION 1612.5, SHALL BE SUBMITTED TO THE BUILDING |
| | OFFICIAL. |
| | |
| | ON 09/07/2016 A #114 INSPECTION WAS PASSED (SLAB) |
| | DEPENDING ON WHAT SLAB WAS POURED THE 2ND ELEVATION |
| | CERTIFICATE WOULD BE REQUIRED. |
| | |
| | (3RD ) ELEVATION CERTIFICATE REQUIRED. 110.3 110.6 |
| | REQUIRED INSPECTIONS.FINAL. TO BE MADE AFTER THE |
| | BUILDING IS COMPLETED AND READY FOR OCCUPANCY. |
| | 6.1. LOWEST FLOOR ELEVATION. IN FLOOD HAZARD AREAS, AS |
| | PART OF THE FINAL INSPECTION, A FINAL CERTIFICATION OF |
| | THE LOWEST FLOOR ELEVATION SHALL BE SUBMITTED TO THE |
| | AUTHORITY HAVING JURISDICTION. |
| | PLEASE NOTE ON THE 3RD FLOOD ZONE CERTIFICATE SECTION |
| | C2 LINE E AND SECTION D AND ATTACHED PHOTOS WILL BE |
| | WHERE GENERATOR PADS, THE TOWER FOUNDATION INFORMATION |
| | WILL NEED TO BE PLACED AND ELEVATIONS WHERE THE COAX |
| | CABLE ENTERS THE BUILDING, THE HEIGHT OF THE ANTENNA |
| | ETC... |
| | |
| | WITH THE ANTENNA COMING IN( AS A REVISION NOT A |
| | SEPARATE PERMIT) WITH THE TOP OF THE FOUNDATION BELOW |
| | THE BASE FLOOD, THIS I HAD A CONCERN ABOUT. TAKING IT |
| | TO THE ASSISTANT BUILDING OFFICIAL DOUG HARVEY WAS OK |
| | WITH THAT SINCE THE BOLTS, TOWER ARE MADE OF GALVANIZED |
| | METAL. HE WAS CONCERNED THAT THE FLOOD ZONE CERTIFICATE |
| | NEEDED TO SHOW THE COAX CABLE ENTERING ABOVE THE |
| | REQUIRED 8 FEET NGVD. THIS SHOULD SHOW UP ON THE 3RD |
| | REQUIRED ELEVATION CERTIFICATE UNDER THE SECTION C2 AND |
| | SECTION D AND PHOTOS. |
| | |
| | A HOLD OR LOCK HAS BEEN PUT ON THE PERMIT 16010466 FOR |
| | THE CERTIFICATE OF COMPLETION/ OR OCCUPANCY UNTIL THE |
| | 3RD FLOOD ZONE CERTIFICATE IS RECEIVED, REVIEWED AND |
| | APPROVED BY THE CITY. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |