| 2016-09-22 18:54:25 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | PROJECT NAME: |
| | JOB ADDRESS: 3912 GREENWOOD AVENUE |
| | DESCRIPTION: INTERIOR RENOVATIONS |
| | MASTER PERMIT: 16080928 |
| | |
| | BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS. |
| | ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF |
| | SUBMITTED CORRECTIONS. |
| | |
| | 1. AN ELECTRICAL SUB PERMIT IS REQUIRED. |
| | 2. THIS PROPERTY IS ZONED SINGLE FAMILY AND THEREFORE |
| | JUST LIKE THE SECOND KITCHEN IS NOT ALLOWED, NEITHER IS |
| | THE SECOND ELECTRICAL METER. CORRECT THE PLANS |
| | ACCORDINGLY. |
| | 3. THE RISER DIAGRAM AS SUBMITTED DOES NOT COMPLY WITH |
| | CODE REQUIREMENTS, AND DOES NOT SPECIFICALLY REFLECT |
| | THE SITE CONDITIONS AS SHOWN ON PLANS. YOU ARE ONLY |
| | ALLOWED ONE SERVICE LATERAL OR DROP. |
| | 4. THE CORRECTED RISER MUST INCLUDE THE INTER-SYSTEM |
| | BONDING TERMINAL AND CONDUCTOR INSULATION TYPE, AND |
| | PANEL TYPE. INDOOR OR OUTDOOR ETC. |
| | 5. CORRECT THE PANEL SCHEDULE TO SHOW THE OVERCURRENT |
| | PROTECTION FOR THE SUB PANEL (B). |
| | 6. BOTH PANEL SCHEDULES INDICATE LOCATION AS IN THE |
| | GARAGE; THIS DOES NOT MATCH THE DRAWINGS. |
| | 7. ACCORDING TO THE SAME PANEL SCHEDULES THEY CALL FOR |
| | FLUSH MOUNTED PANELS, YET THE DRAWINGS INDICATE A |
| | SURFACE MOUNTED. |
| | 8. CORRECT THE LOAD CALCS TO MATCH THE CORRECTED RISER |
| | AND SITE DEMANDS. |
| | 9. WATER HEATER IS REQUIRED IN THE DWELLING. YOU SHOW |
| | AS OPTIONAL. YOU HAVE TO DECIDE AS THE LOAD CALCS FOR |
| | THIS HAVE TO BE INCLUDED. FURTHERMORE INDICATE WHETHER |
| | THEY ARE GOING TO BE GAS OR ELECTRIC. |
| | 10. CORRECT THE LOAD CALCS FOR PANEL B TO REMOVE THE |
| | RANGE LOAD AND CIRCUIT. |
| | 11. SHEET M1 SHOWS THE POWER REQUIREMENTS FOR THE HVAC |
| | EQUIPMENT IS 208/230; THE HOUSE SERVICE IS 120/240 |
| | CORRECT THIS ACCORDINGLY. |
| | 12. GAS METER SHALL BE FURTHER THAN 10? FROM EITHER THE |
| | ELECTRICAL PANEL OR METER SOCKET. |
| | 13. SHEET M1 REFLECTS A SECOND GAS METER ON THE |
| | EXTERIOR OF THE GARAGE WHICH DOES NOT APPEAR ON SHEET |
| | E1. WHICH IS CORRECT? |
| | 14. BOXES USED AT LUMINAIRE OR LAMPHOLDER OUTLETS IN A |
| | CEILING SHALL BE REQUIRED TO SUPPORT A LUMINAIRE |
| | WEIGHING A MINIMUM OF 50 LB. ADD THIS TO THE NOTES ON |
| | CEILING BOXES ON PAGE. |
| | 15. BOXES USED FOR THE SOLE SUPPORT OF CEILING FANS |
| | SHALL BE MARKED BY THE MANUFACTURER AS SUITABLE FOR THE |
| | PURPOSE, AND INDICATE THE WEIGHT LIMITATIONS BUT SHALL |
| | NOT BE USED TO SUPPORT PADDLE FANS HEAVIER THAN 70 LBS. |
| | 16. IN DWELLING UNITS, AT LEAST ONE RECEPTACLE OUTLET |
| | SHALL BE INSTALLED IN BATHROOMS WITHIN 3 FT. OF THE |
| | OUTSIDE EDGE OF EACH BASIN. |
| | 17. YOU SHALL MARK THE PLANS WITH THE DRAWING SCALE |
| | USED AND THE COMPASS ARROW. |
| | 18. THE PLANS SHOW THE HVAC EQUIPMENT INSIDE THE ATTIC. |
| | AT LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR |
| | CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE |
| | THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT |
| | REQUIRING SERVICING. THE LIGHTING OUTLET SHALL BE |
| | PROVIDED AT OR NEAR THE EQUIPMENT REQUIRING SERVICING. |
| | I SUGGEST THAT THIS SWITCH HAVE A PILOT LIGHT TO |
| | INDICATE IF THE ATTIC LIGHT IS ON. |
| | 19. A 125 VOLT, SINGLE-PHASE, 15 OR 20-AMPERE-RATED |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE |
| | LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE |
| | RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE |
| | EQUIPMENT. |
| | 20. BECAUSE THE BATHROOMS DO NOT HAVE WINDOWS, THE |
| | EXHAUST FAN IS REQUIRED THEREFORE IT SHALL COME ON |
| | WHENEVER THE ROOM IS OCCUPIED AND THUS CONNECTED TO THE |
| | LIGHT SWITCH. IF THE FAN IS LESS THAT 50CFM IT SHALL |
| | HAVE CONTINUOUS OPERATION AND THUS BE NON-SWITCHED. |
| | 21. IN ALL AREAS SPECIFIED IN 210.52, ALL 125-VOLT, 15 |
| | AND 20 AMPERE RECEPTACLES SHALL BE LISTED TAMPER |
| | RESISTANT RECEPTACLES. |
| | 22. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, |
| | SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN |
| | FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, |
| | LIBRARIES, DENS, BEDROOMS, SUNROOMS, RECREATIONS ROOMS, |
| | CLOSETS, HALLWAYS AND SIMILAR ROOMS OR AREAS SHALL BE |
| | PROTECTED BY A COMBINATION TYPE ARC-FAULT CIRCUIT |
| | INTERRUPTER INSTALLED TO PROVIDE PROTECTION OF THE |
| | BRANCH CIRCUIT. |
| | 23. PERMANENTLY CONNECTED APPLIANCES OF OVER 300 VA OR |
| | 1/8 HP REQUIRE A DISCONNECT WITHIN SIGHT OF THE |
| | APPLIANCE. THIS APPLIES TO BOTH WATER HEATERS AND HVAC |
| | EQUIPMENT. |
| | 24. BECAUSE OF THE GAS APPLIANCES YOU ARE TO COMPLY |
| | WITH THE CARBON MONOXIDE DETECTOR REQUIREMENTS. |
| | 25. A MINIMUM OF 75% OF THE LAMPS IN PERMANENTLY |
| | INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY |
| | LAMPS OR A MINIMUM OF 75% OF THE PERMANENTLY INSTALLED |
| | LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH EFFICIENCY |
| | LAMPS |
| | |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |