| Plan Review Notes For Permit 16080912 |
| Permit Number |
16080912 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-08-24 10:01:22 | 906 GRANT STREET | | | PERMIT #16080912 | | | TRACKING # | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | THE PLANS INDICATE AN INCORRECT ADDRESS OF "906 GRAND | | | STREET." | | | | | | NO PRODUCT CUTSHEETS SUBMITTED. | | | | | | NO SITE PLAN PROVIDED SHOWING THE LOCATION OF THE | | | BUILDING. | | | | | | SEVERAL VISUAL APPLIANCES INDICATE A CANDELA OF 102CD. | | | | | | NO MANUAL PULL STATIONS PROVIDED ON FIRST FLOOR. | | | | | | SHEET FA-2: WHY IS THE ANNUNCIATOR PANEL LOCATED INSIDE | | | DWELLING UNIT #110? | | | | | | SHEET FA-8: NOTE 5 INDICATES "BATTERY BACK-UP OF | | | 4-HOURS OF SUPERVISORY MODE" IS NEEDED. NFPA 72 | | | REQUIRES 24-HOURS OF A SECONDARY POWER SUPPLY IN | | | STANDBY MODE. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] |
|