| 2016-10-25 08:56:44 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16080906 |
| | ADD: 1801 N. FLAGLER DR. SUITE # 532 |
| | CONT: COPPERSTONE |
| | TEL: 561-628-7891 |
| | E-MAIL: ???????? PLEASE PROVIDE E-MAIL ADDRESS, THAT IS |
| | HOW WE COMUNICATE TO THE CONTRACTOR. |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: TUES. OCT. 25/2016 |
| | ACTION: DENIED |
| | |
| | 1) THE CONTRACTOR WHICH IS THE AUTHOR OF THE PLANS HAS |
| | NOT PRINTED THEIR NAME, SIGNED THEIR NAME NOR LICENSE |
| | NUMBER. 107.3.4.3 CERTIFICATIONS BY CONTRACTORS |
| | AUTHORIZED. THERE ARE NO FLOOR PLANS WHERE THE CGC HAS |
| | TAKEN OWNERSHIP OF THE DESIGNED PLAN BY PRINTING THEIR |
| | NAME, SIGNING THEIR NAME AND LICENSE NUMBER TO THE |
| | DOCUMENT. |
| | |
| | 2) THE PLANS SUBMITTED INDICATE THE INSTALATION OF TILE |
| | IN THE BATHROOM. THE FLOOR INSULATION PRODUCT SUBMITTED |
| | QUIET CORK HAS NOT SUBMITTED THE REQUIRED (3) TEST |
| | REPORTS. |
| | BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B |
| | 2014) |
| | FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO |
| | HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES |
| | TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS |
| | LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH |
| | CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | 2A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 2B) FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 2C) QEP HAS NO FIRE TESTING, THE REPORT SUBMITTED BY |
| | BADGER CORK HAS BEEN BOUGHT OUT BY ANOTHER COMPANY, QEP |
| | HAS TO HAVE THIER OWN FIRE TESTING REPORT. |
| | FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. INSULATION |
| | INSTALLED BETWEEN A FINISHED FLOOR AND SOLID DECKING |
| | WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED TO HAVE A |
| | FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |