| Plan Review Notes For Permit 16080856 |
| Permit Number |
16080856 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-08-24 11:27:10 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | - PASSED WITH THE FOLLOWING PROVISO | | | | | | 1] THE SERVICE DISCONNECTING MEANS SHALL HAVE A RATING | | | OF NOT LESS THAN 60 AMPERES. NEC 230.79(D) RED-LINED ON | | | PLANS. |
|