| Plan Review Notes For Permit 16080855 |
| Permit Number |
16080855 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-08-23 08:12:55 | RE-ROOF BUILDING REVIEW COMMENTS. | | | CODE: FBC-5TH EDITION (2014). | | | | | | 1- ACCORDING TO SEC. 489.113(3)(G) FLORIDA STATUTES A | | | GENERAL CONTRACTOR WHO IS LICENSED AFTER 1973 CAN NOT | | | DO ROOFING WORK UNLESS HE/SHE IS LICENSED AS A ROOFING | | | CONTRACTOR. ACCORDING TO DBPR THIS CONTRACTOR WAS | | | LICENSED ON JUNE 30, 1989. THEREFORE, CAN NOT DO THE | | | ROOFING WORK. NEED ROOFING CONTRACTOR TO APPLY FOR THE | | | JOB. | | | | | | 2- FLAT ROOF: PROVIDE SIGNED AND SEALED RAS 117 | | | CALCULATIONS (2 COPIES WITH ORIGINAL SEAL AND | | | SIGNATURE) AS REQUIRED BY GENERAL LIMITATION #7 OF NOA | | | 14-1030.02 SUBMITTED. NEED THE CALCULATIONS TO MEET THE | | | DESIGN PRESSURES REQUIRED BY SEC. 1609.1 FBC-BUILDING, | | | 5TH EDITION (2014). | | | | | | 3- ROOF TILE: PROVIDE CALCULATIONS SHOWING THE ROOF | | | TILE MOMENT OF RESISTANCE OR ALL ROOF ZONES TO VERIFY | | | THAT 1 SCREW IS ADEQUATE TO RESIST THE WIND LOADS. SEC. | | | 1609.1 FBC-BUILDING. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|