| Plan Review Notes For Permit 16080844 |
| Permit Number |
16080844 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2016-12-28 14:34:57 | 3RD REVIEW FBC-2014 MECHANICAL | | | PERMIT #16080844 | | | 12/28/16 | | | | | | 1) PLEASE REMOVE THE VOIDED M1.0 & M2.0 PLAN SHEETS | | | FROM THE SETS. | | | | | | 2) THE OUTDOOR DRY BULB TEMPERATURE LISTED IN THE LOAD | | | SUMMARY DOESN'T MATCH THE TEMPERATURE USED FOR THE | | | CALCULATIONS. PLEASE NOTE THAT THE ASHRAE HANDBOOK | | | SPECIFIES SUMMER DRY BULB AT 91 DEGREES, AND WINTER DRY | | | BULB AT 45 DEGREES FOR WPB. | | | | | | 3) IT APPEARS THAT THE AC CALCULATIONS ARE SHOWING | | | HIGHER HEAT GAIN AND LOWER HEAT LOSS VALUES THAN THE | | | VALUES SHOWN IN THE SUMMARY LOADS SHOWN ON M2.0- REFER | | | TO SECTION C403.2.2. FBC-14 ENERGY CONSERVATION. | | | | | | 3) THE COMPLIANCE DATA FOR THE AC SYSTEMS- CAPACITIES, | | | DESIGN EFF., AND NUMBER OF RTU'S- LISTED IN THE REVISED | | | ENERGYGAUGE SUBMITTAL DOES NOT MATCH THE AC EQUIPMENT | | | SCHEDULES ON M2.0. ALSO MISSING IS THE COMPLIANCE DATA | | | FOR THE SPLIT SYSTEMS. | | | | | | 4) PROVIDE A FLORIDA PRODUCT APPROVAL OR MIAMI-DADE NOA | | | FOR THE GLOBAL FANS, AND INDICATE THE HEIGHTS FROM THE | | | FLOOR TO THE BOTTOM OF THE FANS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|