2016-12-28 14:34:573RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16080844
 12/28/16
  
 1) PLEASE REMOVE THE VOIDED M1.0 & M2.0 PLAN SHEETS
 FROM THE SETS.
  
 2) THE OUTDOOR DRY BULB TEMPERATURE LISTED IN THE LOAD
 SUMMARY DOESN'T MATCH THE TEMPERATURE USED FOR THE
 CALCULATIONS. PLEASE NOTE THAT THE ASHRAE HANDBOOK
 SPECIFIES SUMMER DRY BULB AT 91 DEGREES, AND WINTER DRY
 BULB AT 45 DEGREES FOR WPB.
  
 3) IT APPEARS THAT THE AC CALCULATIONS ARE SHOWING
 HIGHER HEAT GAIN AND LOWER HEAT LOSS VALUES THAN THE
 VALUES SHOWN IN THE SUMMARY LOADS SHOWN ON M2.0- REFER
 TO SECTION C403.2.2. FBC-14 ENERGY CONSERVATION.
  
 3) THE COMPLIANCE DATA FOR THE AC SYSTEMS- CAPACITIES,
 DESIGN EFF., AND NUMBER OF RTU'S- LISTED IN THE REVISED
 ENERGYGAUGE SUBMITTAL DOES NOT MATCH THE AC EQUIPMENT
 SCHEDULES ON M2.0. ALSO MISSING IS THE COMPLIANCE DATA
 FOR THE SPLIT SYSTEMS.
  
 4) PROVIDE A FLORIDA PRODUCT APPROVAL OR MIAMI-DADE NOA
 FOR THE GLOBAL FANS, AND INDICATE THE HEIGHTS FROM THE
 FLOOR TO THE BOTTOM OF THE FANS.
  