Plan Review Notes
Plan Review Notes For Permit 16080844
Permit Number 16080844
Review Stop B
Sequence Number 3
Notes
Date Text
2017-01-05 12:04:36BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16080844
 ADD: 1101 54TH ST.
 CONT: ALBU & ASSOCIATES
 TEL: 407-788-1450
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 3RD REVIEW
 DATE: THURS. JAN. 056/2017
  
 ACTION : DENIED
 1) MISSING SOILS REPORTS, 2 ORIGINAL SIGNED AND SEALED
 SOILS REPORTS REQUIRED. 2014 FBC-B SECTION 1803.5.2
 QUESTIONABLE SOIL. WHERE THE CLASSIFICATION, STRENGTH
 OR COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR WHERE A
 LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE
 PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION
 BE CONDUCTED.
  
 01/09/2017 RECEIVED FEDEX: 2 SOILS REPORTS, SIGNATURES
 ARE COPIES, YOU CAN SEE PIXELS IN THE SIGNATURE, NEEDS
 TO BE EITHER AN ELECTRONINC SIGNATURE SUBMITTED
 ELECTRONICALLY IN COMPLIANCE WTIH 61G15-23.005
 PROCEDURES FOR SIGNING AND SEALING ELECTRONICALLY
 TRANSMITTED PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS OR SIGNED REPORT IN COMPLIANCE WITH
 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR INDEX
 SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND
 THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE
 PRODUCTION & PREPARATION OF EACH SECTION OF THE
 ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION
 ON THE COVER SHEET OR INDEX LISTING HOW MANY PAGES ARE
 COVERED UNDER THE COVER SHEET OR INDEX SHEET. ..
 CALLED KYLECARR AND LEFT A MESSAGE ON HIS VOICE MAI
 NEED ORIGINAL SIGNED SOILS REPORTSL.
  
  
 BUILDING PROVISOS:
  
 1) THE SUBMITTED 2 INCH BINDERS OF PRODUCT APPROVALS
 HAVE NOT BEEN REVIEWED BY THE DESIGNER OF RECORD NOR
 ANY OF THE SUBMITTED APPROVALS THE COVERSHEETS ONLY
 HAVE THE TECHNICAL SHEETS WERE SUBMITTED. THE PRODUCT
 APPROVALS REQUIRE THE COVERSHEETS INDICATING THEY ARE
 EITHER A FLORIDA APPROVAL OR A MIAMI-DADE NOA (NOTICE
 OF ACCEPTANCE). IF THEY HAVE NEITHER A LOCAL APPROVAL
 MAY BE REQUIRED.
 1A) BUILDING PROVISO: 2014 FLORIDA BUILDING CODE W 2014
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.3.4.2 DEFERRED
 SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, DEFERRED
 SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN
 THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION
 AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL
 WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL
 ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING
 OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS
 ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE
 BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 1B) PROVISO/ DEFERRED SUBMITTAL. 2014 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 1C)PROVISO/ DEFERRED SUBMITTAL. FBC 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 1D) PROVISO/ DEFERRED SUBMITTAL. ROOF TOP A/C STANDS
 WILL REQUIRE A PRODUCT APPROVAL. EITHER THE CONTRACTOR
 OR THE DESIGNER OF RECORD WILL NEED TO COMPLETE THE
 FOLLOWING ON THE PRODUCT APPROVAL IN CALCULATING THE
 AREA OF THE ROOF TOP COMPRESSORS, THE MEAN ROOF HEIGHT
 OF THE STAND AND COMPRESSORS, WEIGHT, CIRCLED THE
 DESIGN PARAMETERS IN THE TABLES , ANCHORS AND UPLIFT
 VERSES MOMENT. 1609.6.4.4.1 COMPONENTS & CLADDING.
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
  
  