| 2016-11-29 14:23:06 | 2ND REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | PREVIOUS COMMENT 2ND REQUEST; | | | 4) SHT. P1.0 REFERS TO CIVIL DRAWINGS. THERE ARE NO | | | CIVIL DRAWINGS IN THE PLANS I REVIEWED. CLARIFY. | | | | | | NEW COMMENTS : | | | | | | 1. PROVIDE THE SQUARE FOOTAGE THAT IS BEING DRAINED BY | | | SCUPPERS, DOWNSPOUTS AND GUTTERS. PER WPB AMEND TO FBC | | | 107.2.1 | | | | | | 2. ALL FLOOR DRAINS REQUIRE A TRAP PRIMER SHOW ON | | | PLANS. PER FBC PL 1002.4 | | | |
|