| 2016-12-06 12:29:32 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16080844 |
| | ADD: 1101 54TH ST. |
| | CONT: ALBU & ASSOCIATES |
| | TEL: 407-788-1450 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2ND REVIEW |
| | DATE: TUES. DEC. 06/2016 |
| | ACTION: DENIED |
| | |
| | 1) PROVISO: ART IN PUBLIC PLACES. |
| | |
| | 2) 2ND REQUEST. THE BUILDING PERMIT FOR THIS PROJECT |
| | INDICATES THE VALUE FOR THE PROJECT OF $2,643,849.00 |
| | DOLLARS. PLEASE NOTE THIS VALUE SHOULD ONLY REFLECT THE |
| | BUILDING, NOT ANY OF THE PERMIT VALUES FOR THE SITE |
| | IMPROVEMENT. |
| | THERE ARE (4) PERMITS THAT WILL COST $80.00 AN |
| | ADMINISTRATIVE FEE, (MECHANICAL, ELECTRICAL, PLUMBING & |
| | ROOFING) THESE VALUES SHOULD REMAIN IN THE BUILDING |
| | PERMIT. THE OTHER PERMITS TO BE REVIEWED UNDER SEPARATE |
| | PERMIT, WITH SEPARATE ASSOCIATED FEES ARE: FIRE |
| | SPRINKLER, FIRE ALARM, ALL LOW VOLTAGE PERMITS, KITCHEN |
| | EXHAUST HOODS, FIRE SUPPRESSION SYSTEMS, WALK IN |
| | COOLERS & FREEZERS, GREASE INTERCEPTORS? |
| | |
| | PERMITS THAT ARE NOT INCLUDED IN THE BUILDING PERMIT |
| | VALUE AND ARE SITE IMPROVEMENT PERMITS WOULD BE |
| | SITE CLEARING PERMITS, UNDERGROUND UTILITIES, LIFT |
| | STATIONS, PAVING AND DRAINAGE, STRIPPING OF PARKING |
| | LOTS, IRRIGATION, LANDSCAPE, SIGN PERMITS AWNINGS? |
| | |
| | 3) COMPLIED. SHEET LS1.0 UNDER THE HEADING CODE |
| | INFORMATION LIST THE WIND DESIGN TO ASCE 7-02. PLEASE |
| | REFER TO THE 2014 FBC-B 1609.1.1 AND CHAPTER 35 THE |
| | REFERENCED STANDARDS ASCE 7-10. |
| | |
| | 4)PROVISO: SHEET LS1.0 UNDER THE HEADING PROJECT USE A |
| | NEW CHEMICAL DEPENDENCY TREATMENT CENTER. THE OCCUPANCY |
| | TYPE A MIXED USE OF BUSINESS & I-1 ALCOHOL AND DRUG |
| | CENTERS). PLEASE BE AWARE IF THERE IS |
| | FOR MEDICAL CARE ON A 24-HOUR BASIS FOR MORE THAN FIVE |
| | PERSONS WHO ARE INCAPABLE OF SELF-PRESERVATION |
| | (DETOXIFICATION FACILITIES) THEN THE OCCUPANCY |
| | CLASSIFICATION WILL BE INSTITUTIONAL GROUP I-2. 2014 |
| | FBC-B 308.4. RESPONSE INDICATES SEE ATTACHED LETTER |
| | FROM MS. BRYN WESCH. |
| | |
| | 5) NOT APPLICABLE. |
| | |
| | 6-19) COMPLIED. |
| | |
| | 20A) BUILDING PROVISO: 2014 FLORIDA BUILDING CODE W |
| | 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 107.3.4.2 DEFERRED |
| | SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, DEFERRED |
| | SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN |
| | THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION |
| | AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL |
| | WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL |
| | ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING |
| | OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS |
| | ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE |
| | BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 20B) PROVISO/ DEFERRED SUBMITTAL. 2014 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE |
| | 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 20C)PROVISO/ DEFERRED SUBMITTAL. FBC 107.3.4.1 PRODUCT |
| | APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE |
| | DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 21) PROVISO/ DEFERRED SUBMITTAL. ROOF TOP A/C STANDS |
| | WILL REQUIRE A PRODUCT APPROVAL. EITHER THE CONTRACTOR |
| | OR THE DESIGNER OF RECORD WILL NEED TO COMPLETE THE |
| | FOLLOWING ON THE PRODUCT APPROVAL IN CALCULATING THE |
| | AREA OF THE ROOF TOP COMPRESSORS, THE MEAN ROOF HEIGHT |
| | OF THE STAND AND COMPRESSORS, WEIGHT, CIRCLED THE |
| | DESIGN PARAMETERS IN THE TABLES , ANCHORS AND UPLIFT |
| | VERSES MOMENT. 1609.6.4.4.1 COMPONENTS & CLADDING. |
| | 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| | MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| | METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| | EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| | AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| | EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| | OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| | LOADS. |
| | |
| | 22) PALM BEACH COUNTY IMPACT FEES/ COMPLIED. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | |