| 2016-11-16 08:40:56 | |
| | 1) SHT. A2.4 - DETAIL # 22 SHOWS THE HEIGHT OF THE |
| | WATER CLOSETS AS 18 INCHES MINIMUM ABOVE THE FINISH |
| | FLOOR.THE SEAT HEIGHT OF A HANDICAPPED WATER CLOSET |
| | SHALL BE 17-19 INCHES ABOVE THE FINISH FLOOR. FAC |
| | SEC.604.4. |
| | 2) INDICATE THE SIZE OF THE ROOF GUTTERS. THE GUTTERS |
| | SHALL BE SIZED IN ACCORDANCE WITH TABLE 1106.6 & TABLE |
| | 1106.7 OF THE FPC. PROVIDE THE HEAD IN INCHES AND THE |
| | WEIR LENGTH. |
| | 3) SHT. 1.4 SHOWS OVERFLOW SCUPPERS BUT WHAT ABOUT |
| | PRIMARY ROOF DRAINAGE? PROVIDE DETAILS. |
| | 4) SHT. P1.0 REFERS TO CIVIL DRAWINGS. THERE ARE NO |
| | CIVIL DRAWINGS IN THE PLANS I REVIEWED. CLARIFY. |
| | 5) SHT. P1.2 REFERS TO THE LENGTH OF THE GAS PIPING AS |
| | BEING LESS THAN 400 FT. THIS IS TOO VAGUE AND A |
| | COMPREHENSIVE GAS REVIEW CANNOT BE DONE. THE TOTAL |
| | DISTANCE FROM THE POINT OF DELIVERY IS REQUIRED TO |
| | CHECK THE TOTAL SIZING OF THE SYSTEM.FGC SEC.402.3. |
| | 6) SHT. P5.1 - CLEANOUTS ARE REQUIRED IN STACKS PER |
| | 2014 FPC SEC. 708.3.4. |
| | 7) SHT. P5.1 - SIZE THE VENTS FOR THE WASHING MACHINE, |
| | THE MOP SINK AND THE FLOOR DRAIN. |
| | 8) SHT. P5.1 - THE WASHING MACHINE SHALL BE INSTALLED |
| | ON A 3 INCH STACK PER THE 2014 FPC 406.2. |
| | 9) SUBMIT SIZING CALCULATIONS FOR THE GREASE |
| | INTTERCEPTOR. FPC 1003.2. |
| | 10) VENTS SHALL CONNECT TO THE HORIZONTAL DRAIN IN |
| | ACCORDANCE WITH 2014 FPC SEC.905.3. FLAT, DRY VENTS ARE |
| | NOT PERMITTED. |
| | 11) THE GAS TABLE REFERRED TO IS FOR GALVANIZED PIPE. |
| | GALVANIZED PIPE CANNOT BE INSTALLED UNDERGROUND PER |
| | 2014 FGC SEC.404.11. |
| | 12) HOSE BIBBS SHALL BE EQUIPPED WITH SHUTOFF VALVES |
| | PER 606.2. |
| | 13) SHUTOFF VALVES SHALL BE INSTALLED ON THE COLD WATER |
| | INLET TO THE TANKLESS WATER HEATERS PER 2014 FPC |
| | SEC.606.1. |
| | 14) SHT. P1.2 - THE FIXTURES IN TOILET ROOMS #107, 108, |
| | 109 & 110 ARE MISLABELED ON THE FLOOR PLAN AND THE |
| | RISER. |
| | |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |