| 2016-08-30 08:57:39 | 1ST REVIEW FBC-2014 MECHANICAL |
| | PERMIT #16080844 |
| | 8/30/16 |
| | |
| | 1) SUBMIT AC COOLING AND HEATING CALCULATIONS IN |
| | ACCORDANCE WITH THE REQUIREMENTS OF SECTION C403.2.1 |
| | FBC-14 ENERGY CONSERVATION. |
| | |
| | 2) ADVISORY: SEPARATE PERMITS AND PLAN SUBMITTALS ARE |
| | REQUIRED FOR THE KITCHEN HOODS, THE FIRE SUPRESSION |
| | SYSTEM, AND THE WALK-IN COOLER AND FREEZER. |
| | |
| | 3) THE OUTSIDE AIR CALCULATIONS ARE MISSING THE RATES |
| | FOR THE MEDICAL ROOMS INCLUDING THE DOCTOR'S AND NURSES |
| | OFFICES AND WORKROOMS, THE BEDROOMS, THE CLASSROOM, THE |
| | LOUNGES, THE LAUNDRY, THE CORRIDORS, AND THE MASSAGE |
| | ROOM ETC. |
| | |
| | 4) THE AIR DEVICE SCHEDULE IS MISSING THE ERC'S. |
| | |
| | 5) FIRE DAMPERS MISSING: A) 18X14 SUPPLY AND RETURN |
| | DUCTS PENETRATING THE OPEN OFFICE/BREAKROOM AND STORAGE |
| | WALLS. B) 22X14 SUPPLY AND 20X14 RETURN DUCTS |
| | PENETRATING THE CORRIDOR WALL ABOVE DOOR #20. C) 22" |
| | DIAMETER DUCT PENETRATING THE CORRIDOR WALL ABOVE DOOR |
| | #45 |
| | |
| | 6) THE RETURN TRANSFER OVER DOOR #45 AND THE OTHER |
| | TRANSFERS SHOWN IN THE CORRIDORS OF THE SLEEPING ROOMS, |
| | AND IN CORRIDOR 137 ARE PROHIBITED PER SECTION 601.2. |
| | |
| | 7) ADVISORY: ALL DOORS ENCLOSING MECHANICAL CLOSETS |
| | SHALL BE ON NON-COMBUSTIBLE MATERIALS UNLESS THE RETURN |
| | SYSTEM TO THE AIR HANDLERS IS DUCTED- SECTION |
| | C403.2.7.2 FBC-14 ENERGY CONSERVATION. |
| | |
| | 8) SHOW THE LOCATIONS OF THE SPLIT SYSTEM CONDENSERS |
| | AND PROVIDE WIND LOAD ENGINEERING AND DESIGN CRITERIA |
| | FOR ALL EXTERIOR MECHANICAL APPLIANCES AND EQUIPMENT- |
| | SECTION 301.15. PLEASE NOTE THAT NOA #12-0327.05 SHOWN |
| | ON SHEET M1.0 HAS BEEN REVISED TO NOA #14-1224.10. |
| | PLEAS SUBMIT A COPY OF THE NOA WOTH SHOP DRAWING |
| | APPROVAL STAMP AND SIGNATURE BY THE EOR. |
| | |
| | 9) PROVIDE EQJUIPMENT SCHEDULES AND SUBMITTALS FOR THE |
| | MOTORIZED DAMPERS AND OUTSIDE AIR AND EXHAUST LOUVER. |
| | INCLUDE NOA'S OR FLORIDA PRODUCT APPROVALS WHERE |
| | REQUIRED FOR WIND AND WEATHERING COMPLIANCE. |
| | |
| | 10) SUBMIT MANUFACTURER SPECIFICATIONS FOR THE LAUNDRY |
| | APPLIANCES. |
| | |