 GAS COMMENTS:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 2. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37).
  
 3. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 4. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 5.THE PLUMBING FIXTURE SPECS STATE THE GWH AT 237,000
 BTU YOUR SHOWING 7 GWH WITH A TOTAL BTU LOAD OF
 1,659,000 THE NOTE ON THE 2PSI PE PIPING FOR GWH STATES
 A TOTAL OF 1,399,000 PLEASE CLARIFY. WPB AMEND TO FBC
 107.2.1
  
 6. IF THE TOTAL BTU LOAD FOR THE HEATERS IS 1,659,00O
 THE PE PIPING WOULD NEED TO BE 11/2 TO THE FIRST TEE.
 PER FBC FG TABLE 402.4(22)
  
 7. THE 2ND SECTION OF PE PIPE IS SHOWN AS 1" IT SHOULD
 BE 11/4. PER FBC FG TABLE 402.4(22)
  
 8. THE TABLE IN YOUR NOTES ON THE 2PSI PE PIPING RISER
 SHOULD BE 402.4(22) NOT 402.4(20).
  
 9. THE NOTE ON THE GAS PIPING UPSTREAM OF THE METER IS
 NOT NEEDED THAT PIPING IS NOT UNDER THE JURISDICTION OF
 THE BUILDING DEPT THAT IS SIZED AND THE PRESSURE
 DETERMINED BY THE GAS UTILITIES COMPANY.
  
 10. THE NOTE ON THE LESS THAN 2PSI SYSTEM FOR KIT CALLS
 OUT 11/4 BUT THE PLAN SHOWS 3/4 PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1