Plan Review Notes
Plan Review Notes For Permit 16080844
Permit Number 16080844
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-09-02 09:52:01THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET LS 1.0 ? THERE IS AN INCORRECT CODE REFERENCE
 UNDER THE HEADING OF CODE INFORMATION; PALM BEACH
 COUNTY LOCAL FIRE CODE AMENDMENTS IS NOT UNDER THE
 JURISDICTION OR ENFORCED BY THE CITY OF WEST PALM BEACH
 FIRE DEPARTMENT.
  
 2) SHEET LS 1.1 ? THERE IS AN INDICATION, ES ?
 ELECTRONIC DOOR SECURITY RELEASE BUTTON, ON SEVERAL
 EXIT DOORS. ANY SECURITY DEVICE SHALL COMPLY WITH THE
 APPLICABLE REQUIREMENTS OF NFPA 101, CHAPTER 7, MEANS
 OF EGRESS.
  
 PLEASE PROVIDE A CONFIRMATION NOTE.
  
 ANY INSTALLATION OF ELECTRONIC SECURITY DEVICES SHALL
 BE SUBMITTED UNDER SEPARATE SHOP DRAWINGS WITH
 APPLICABLE MANUFACTURER?S SPECIFICATION SHEETS AND
 FUNCTIONALITY STEPS.
  
 3) SHEET A 4.2 ? DOORS # 3 ARE INDICATED AS BEING 20
 MIN FIRE RATING IN THE DOOR SCHEDULE ON SHEET A6.2.
 SHEET LS 1.1 INDICATES DOORS # 3 AS 45 MIN FIRE RATING.
  
 PLEASE REVIEW, CLARIFY AND CORRECT TO THE PROPER FIRE
 RATING.
  
 4) SHEET A 4.2 ? DOORS # 5 ARE INDICATED AS BEING 20
 MIN FIRE RATING IN THE DOOR SCHEDULE ON SHEET A6.2.
 SHEET LS 1.1 INDICATES DOORS # 5 AS 45 MIN FIRE RATING.
  
 PLEASE REVIEW, CLARIFY AND CORRECT TO THE PROPER FIRE
 RATING.
  
 5) SHEET A 4.1 ? DOORS # 5 ARE INDICATED AS BEING 20
 MIN FIRE RATING IN THE DOOR SCHEDULE ON SHEET A6.2.
 SHEET LS 1.1 INDICATES DOORS # 5 AS 45 MIN FIRE RATING.
  
 PLEASE REVIEW, CLARIFY AND CORRECT TO THE PROPER FIRE
 RATING.
  
 6) SHEET A 4.1 ? DOOR # 8 IS INDICATED AS BEING 20 MIN
 FIRE RATING ON SHEET LS 1.1. IN THE DOOR SCHEDULE ON
 SHEET A6.2 THERE IS NO INDICATION OF A FIRE RATING.
  
 PLEASE REVIEW, CLARIFY AND CORRECT TO THE PROPER FIRE
 RATING.
  
 7) SHEET A 4.2 ? DOOR # 13 IS INDICATED AS BEING 20 MIN
 FIRE RATING IN THE DOOR SCHEDULE ON SHEET A6.2. SHEET
 LS 1.1 INDICATES DOORS # 5 AS 45 MIN FIRE RATING.
  
 PLEASE REVIEW, CLARIFY AND CORRECT TO THE PROPER FIRE
 RATING.
  
 8) SHEET A 4.3 ? DOORS # 3 TO THE STORAGE ROOMS ARE
 INDICATED AS BEING 20 MIN FIRE RATING IN THE DOOR
 SCHEDULE ON SHEET A6.2. SHEET LS 1.1 INDICATES DOORS #
 3 AS 45 MIN FIRE RATING.
  
 PLEASE REVIEW, CLARIFY AND CORRECT TO THE PROPER FIRE
 RATING FOR A STORAGE ROOM.
  
 9) SHEET A 4.1 ? THE NORTH AREA 1 HOUR WALL SEPARATION
 INDICATES WALL DESIGN P7C. SHEET A 6.1 INDICATES ONLY A
 P7.
  
 PLEASE CONFIRM THIS WALL DESIGN, POSSIBLE CONFLICT
 NOTED BELOW.
  
 10) SHEET A 4.3 INDICATES THE CORRIDOR WALLS AS P7.
 SHEET A 6.1 INDICATES THE P7 RATING AS GOING ONLY TO A
 RATED CEILING. THERE IS NO RATED CEILING CALL OUT
 INDICATION IN THE CORRIDOR AREA.
  
 PLEASE REVIEW, CLARIFY AND CORRECT TO AN APPLICABLE
 CALL OUT FIRE RATING.
  
 11) SHEET A 4.2 ? THERE IS SEPARATION WALL IN THE
 CENTER AREA THAT IS INDICATED AS P7C. THERE IS NO P7C
 INDICATED ON SHEET A 6.1.
  
 HOWEVER, SHEET LS 1.1 INDICATES THIS CENTER WALL AS A
 SOLID LINE 1 HOUR FIRE RATING GOING TO THE BOTTOM SIDE
 OF THE ROOF DECK.
  
 PLEASE REVIEW, CLARIFY AND CORRECT TO AN APPLICABLE
 CALL OUT FIRE RATING.
  
 12) SHEET A 3.1 ? BUILDING SECTION 3 INDICATES A
 CEILING FIRE RATING ULP522. THERE IS NO UL DESIGN CALL
 OUT DETAIL THAT CAN BE IDENTIFIED IN THE PLAN SHEETS.
  
 ADDITIONALLY, THERE ARE NO INDICATIONS OR DESIGN
 LIMITATIONS OR BOUNDARIES FOR ANY FIRE RATING CEILING
 ASSEMBLY AREAS.
  
 PLEASE REVIEW, CLARIFY AND PROVIDE THE SPECIFIC AREA
 BOUNDARIES OF ANY FIRE RATED CEILING AREAS.
  
 13) SHEET H 1.0 ? A HOOD SYSTEM IS INDICATED. ANY HOOD
 SYSTEM OR SUPPRESSION SYSTEM SHALL COMPLY WITH THE
 REQUIREMENTS OF NFPA 96 AND SHALL BE SUBMITTED UNDER A
 SEPARATE PERMIT AND SHOP DRAWINGS.
  
 THE HOOD SYSTEM AND SUPPRESSION SYSTEM IS NOT APPROVED
 UNDER THIS PERMIT.
  
 PLEASE PROVIDE A NOTE OF CONFIRMATION WITH THE ABOVE.
  
 14) REPEATED COMMENT - SHEET E 3.0 - A HOOD SYSTEM IS
 INDICATED. ANY HOOD SYSTEM OR SUPPRESSION SYSTEM SHALL
 COMPLY WITH THE REQUIREMENTS OF NFPA 96 AND SHALL BE
 SUBMITTED UNDER A SEPARATE PERMIT AND SHOP DRAWINGS.
  
 THE HOOD SYSTEM AND SUPPRESSION SYSTEM ARE NOT APPROVED
 UNDER THIS PERMIT.
  
 PLEASE PROVIDE A NOTE OF CONFIRMATION WITH THE ABOVE.
  
 15) SHEET E 5.0 ? A GENERATOR IS INDICATED. THE
 GENERATOR INSTALLATION SHALL COMPLY WITH THE
 REQUIREMENTS OF NFPA 110, STANDARD FOR EMERGENCY AND
 STANDBY POWER SYSTEMS.
  
 THE GENERATOR INSTALLATION IS NOT APPROVED UNDER THIS
 PERMIT.
 THE GENERATOR INSTALLATION SHALL BE SUBMITTED UNDER
 SEPARATE SHOP DRAWINGS.
  
 16) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  